Electrical Connection
SMA Solar Technology AG
36
SC-100-IEN093231
Installation Guide
NOTICE!
The DC voltage of the PV generator must never exceed the maximum permissible inverter
input voltage.
Otherwise the inverter is in acute danger when connected! U
PV
< 900 / 1000 V!
NOTICE!
All cable feeds and base plates must be locked tightly so that no small animals can enter
the device!
NOTICE!
Since the Sunny Central is not equipped with a fuse, the DC cables to be connected must
be designed for at least 2/3 of the maximum generator current rating.