4.3 Storage
/05*$&
Improper storage can cause moisture to seep into the Sunny Central.
Damage to the Sunny Central.
• The Sunny Central must be closed during storage.
• If stored for 6 months or longer, make sure the storage area is dry.
• The storage temperature has to be between − 13°F to 140°F ( − 25°C to +60°C).
/05*$&
Uneven underground can damage the frame construction.
• The underground must be suitable for the weight of the inverter of 1,800 kg.
• The underground may only deviate from a level of 0.25%.