2 ac connection – SMA SC 100LV-560HE User Manual
Page 87

SMA Solar Technology AG
Appendix D - Cable cross section and Torque
Installation Guide
SC125_560HE-IEN083220
87
12.2 AC connection
(1
Screw at NH fuse holder
(2
Copper bus bar perforated
(3
Bolt clamp
(4
Screw at fuse switch disconnector
(5
EriFlex bus bar perforated
Sunny Central
AC terminals
Max. cross
section
Torque
SC 100LV
5 x WFF 185
M12
(3
up to 240 mm²
14 - 31 Nm
SC 125LV
5 x WFF 185
M12
(3
up to 240 mm²
14 - 31 Nm
SC 150 Standard
5 x WFF 185
M12
(3
up to 240 mm²
14 - 31 Nm
SC 200 Standard
5 x WFF 185
M12
(3
up to 240 mm²
14 - 31 Nm
SC 200HE
Isolator
M12
(4
up to 240 mm²
32 Nm
SC 250 Standard
5 x WFF 185
M12
(3
up to 240 mm²
14 - 31 Nm
SC 250HE
Isolator
M12
(4
up to 240 mm²
32 Nm
SC 350 Standard
3 x Cu
Cu M12
(2
3 x 240 mm² per
phase
74 Nm
SC 350HE
3 x Cu
Cu M12
(2
3 x 240 mm² per
phase
74 Nm
SC 500HE
Isolator
M16
(5
up to 300 mm²
210 Nm
SC 560HE
Isolator
M16
(5
up to 300 mm²
210 Nm