Requirements for the Installation
Installation Guide
SMC50_60-11:SE2006
Page 23
The indicated power on the x axis complies approx. 6.2 kW per phase.
In consequence you should install only one Sunny Mini Central 5000/6000 per
phase. To install a plant with a higher power that does not stop feeding because of
AC over voltage, you should check the connection conditions of the Sunny Mini Cen-
tral 5000/6000 (e. g. by using a cable with a higher cross-section).
Example
The grid voltage without feeding averages 230 V.
The grid impedance at the connection point averages 1.2 Ohm.
Grid Impedance [Ohm]
Power [kW] per Phase
0
5
10
15
20
25
30
0,5
0,6
0,7
0,8
0,9
1,0
1,1
1,2
1,3
1,4
1,5
230 V