Eaton Electrical Powerware 5130 Rack/Tower UPS 1250-3000 VA User Manual

Page 49

Advertising
background image

ADDITIONAL UPS FEATURES

EATON Powerware

®

5130 Rack/Tower UPS (1250–3000 VA) User’s Guide

S 164201730 Rev 2

www.powerware.com

43

Customizing the UPS with the UPS Configuration Tool

To customize the UPS settings:

1.

Download the UPS Configuration tool from www.powerware.com.

2.

Follow the on-screen instructions for the Powerware 5130.

It is possible to modify the settings listed below (detailed
comments are available in the UPS Configuration tool).

Table 5. Main Output Options

Function

Factory Setting

Other Available Settings

Low-Voltage Models. Output voltage on
battery power

120 Vac

100/120/127 Vac

High-Voltage Models. Output voltage on
battery power

230 Vac

200/208/220/240 Vac

PW5130G3000-XL2U Models. Output
voltage on battery power

208V

All Models. Overload alarm threshold

105%

30/50/70%

Table 6. Voltage Threshold Options

Low-Voltage Model Function

Factory Setting

Other Available Settings

High threshold for transfer to battery

151 Vac ±3%

141–153 Vac

Low threshold for transfer to battery

89 Vac ±3%

89–94 Vac

Fader activation threshold

132 Vac ±3%

127–138 Vac

Booster activation threshold

102 Vac ±3%

92–108 Vac

Maximum input-voltage range

Disabled

Enabled

1

High-Voltage Model Function

Factory Setting

Other Available Settings

High threshold for transfer to battery

294 Vac

271–294 Vac

Low threshold for transfer to battery

160 Vac

160–180 Vac

Fader activation threshold

265 Vac

244–265 Vac

Booster activation threshold

184 Vac

184–207 Vac

Maximum input-voltage range

Disabled

Enabled

2

1

Low threshold for transfer to battery is 70V.

2

Low threshold for transfer to battery is 150V.

Advertising