Wall-Mounted Dewpoint Sensor

Product Information Sheet

210-2002

•

Set the Low End Point field to 0.

•

Set the HighEnd Point field to 5.0.

•

Set the Low Eng. Units field to 0.

•

Set the High Eng. Units field to 80.

•

Set the Low End Limit field to -0.5.

•

Set the HighEnd Limit field to 6.5.





REFLECS

1.

Log in to the controller.



2.

From the Main Menu, select 4 -Sensor

Control.


3.

From the Sensor Control screen, select 2 -

Setup.



4.

From the Select Sensor screen, choose the

sensor you wish to set up:



5.

Once you select a sensor, the Sensor Setup

screen opens. Enter a name for the sensor in
the Name field (for example, DEWPOINT)

and set the Type field to Linear by using the

scroll keys or pressing the red button + the

(L) button.


6.

Press 0 to go back to the Sensor Control

screen. Select 3 -Setpoints and then choose

the sensor to set Gain and Offset.

Analog Input Screen - Set Sensor Properties

REFLECS Login Screen

REFLECS Main Menu Screen

Sensor Control Screen

Select Item Screen

Sensor Control Screen