2 mrlds dimensions, 3 mrlds analog version (809-100x), 1 network layout – Emerson MRLDS User Manual

Page 9: 2 mrlds wiring, 2 mrlds d, Imensions, Etwork, Ayout, 2 mrlds w, Iring

Advertising
background image

MRLDS Dimensions

MRLDS Analog Version (809-100x)

3

2.2

MRLDS Dimensions

3

MRLDS Analog

Version (809-100x)

3.1

Network Layout

3.2

MRLDS Wiring

For analog MRLDS units, connect to a MultiFlex

board via the analog input (use Belden 8761 cable).

Figure 2-2

- Attaching and Removing Cover

Figure 2-3

- MRLDS Mounting Dimensions

Figure 3-1

- Analog MRLDS Network Layout Example

Figure 3-2

- Analog MRLDS Wiring

E2

MRLDS Units

I/O Net

MultiFlex Board

To

O

th

er

I/O

N

et

De

vic

es

ANALOG MRLDS -
INSIDE LOWER PORTION
OF BASE

MULTIFLEX BOARD -
LOWER RIGHT CORNER

INPUT 13

INPUT 14

INPUT 15

INPUT 16

1

2

3

4

5

6

7

8

0V

SIG

0V

SIG

SIG

SIG

0V

0V

A

C

N

2

4

V

A

C

G

A

S

(+

)

O

U

T

(V

)

TO 24VAC, 10VA
CLASS 2 POWER
SUPPLY

Analog MRLDS
to MultiFlex

A transformer must

be shared

between MRLDS
and the MultiFlex
board. A

must

be used.

If a transformer is
shared between
MRLDS units,
the “ACN” of
each MRLDS
must be wired
to the same
phase of the
transformer.

never

separate

transformer

S

IG

0V

G

ro

u

n

d

O

U

T

(V

)

G

ro

u

n

d

EARTH SHIELD
NEAR THE MULTIFLEX
BOARD.

CONNECT

THE SHIELD TO THE 0V INPUT
ON THE MULTIFLEX BOARD.

DO NOT

Wire MultiFlex SIG to MRLDS OUT(V).
Wire MultiFlex 0V to MRLDS Ground ( ).

BELDEN
8761

BELDEN
8761