THERMOSTAT LOCATION (SG MODELS)

CAUTION — Do not run wire behind ß anges of Header Plate
or in any location where it might be damaged.

Millivolt wall thermostats are specially designed for use on self-
generating systems. They should never be used on line or low
voltage A.C. circuits.

Interior Wall — The thermostat should be installed on an inside
wall away from the furnace but in the same room.

Note: Use 16 gauge wire to prevent excessive loss of milli-
volts.

Proper operation depends on a good pilot ß ame. The ß ame must
cover the top of the thermopile. Cleaning of the pilot oriÞ ce and
burner may be required due to spiders.

System Check (Figure 7)
A millivolt meter is required to check the system. Millivolt
readings should be:

• Across the thermopile terminals, 400-450 millivolts with

thermostat OFF.

• Across the thermopile terminals, 150-250 millivolts with

thermostat ON.

• Across the thermostat wires at the valve, less than 30 millivolts

with thermostat ON.

• Across the thermostat wires at the thermostat, less than 5

millivolts with thermostat ON. (Dirty pilot or low pressure
will reduce readings.)

Connect thermostat wires to gas valve as shown in Figure 7.