• Individual cell voltages

• Overall string voltage

• Ambient temperature immediately surrounding battery

• Battery temperature at several places throughout the

string. Recommend 1 reading per battery stack. More

data points are recommended for larger batteries and to

check for temperature gradients. Readings on the tray,

cell cover or negative terminal are good places to mea-

sure battery temperature. Take readings away from

HVAC sources.

• Float current measured at stack to stack connections

(optional)

• Ohmic measurements (optional). Baseline ohmic read-

ings of individual cells should be taken 6 months from

the date of initial charge.

• Retorque connectors as part of annual maintenance.

ONCE PER YEAR READINGS ARE THE ABSOLUTE

MINIMUM REQUIRED TO PROTECT WARRANTY. More

frequent readings are recommended, especially for critical

sites. Good record-keeping will prevent minor issues from

escalating into more serious problems over time. See

Figure 22 for a sample record-keeping form.

SECTION 16: TAP CONNECTIONS

16.0

Tap Connections

Tap connections are not to be used on a battery. This can

cause overcharging of the unused cells and undercharging

of those cells supplying the load, thus reducing battery life.

SECTION 17: TEMPORARY NON-USE

17.0

Temporary Non-Use

An installed battery that is expected to stand idle longer

than the maximum storage interval (see Section 4.2),

should be treated as stated below. The maximum storage

interval is 6 months if stored at 25°C, 77°F.

Give the battery an equalizing charge as per Section 14.

Following the equalizing charge, open connections at the bat-

tery terminals to remove charger and load from the battery.

Repeat the above after every 6 months (25°C, 77°F) or at

the required storage interval. See Section 4.2 for adjust-

ments to storage intervals when the storage temperature

exceeds 25°C, 77°F.

To return the battery to normal service, re-connect the bat-

tery to the charger and the load, give an equalizing charge

and return the battery to float operation.

SECTION 18: UNIT CLEANING

18.0

Unit Cleaning

Periodically clean cell covers with a dry 2” paintbrush to

remove accumulated dust. If any cell parts appear to be

damp with electrolyte or show signs of corrosion, contact

your local GNB representative.

SECTION 19: MAINTENANCE

19.0

Connections

Battery terminals and intercell connections should be cor-

rosion free and tight for trouble-free operation. Periodically

these connections should be inspected.

CAUTION: DO NOT WORK ON CONNEC-

TIONS WITH BATTERY CONNECTED TO

CHARGER OR LOAD.

If corrosion is present, disconnect the connector from the

terminal.

Gently clean the affected area using a suede brush or

Scotch Brite scouring pad. Apply a thin coating of NO-OX-

ID “A” grease to the cleaned contact surfaces, reinstall

connectors and retorque connections to 11.3 Newton-

meters (100 inch pounds).

All terminal and intercell connections

should be retorqued at least once every year

to 11.3 Newton-meters (100 inch pounds).

NOTE: Design and/or specifications subject to change

without notice. If questions arise, contact your

local sales representative for clarification.

SECTION 20: CAPACITY TESTING

20.0

Capacity Testing

When a capacity discharge test is desired, it is recom-

mended that it be performed in accordance with IEEE-

1188*, latest revision.

An equalizing charge, as described in Section 14.2, must

be performed within 7 days prior to the capacity test. The

batteries must be returned to float charging immediately

after the equalize charge completes.

After the capacity discharge has completed, the batteries

can be recharged in the shortest amount of time by fol-

lowing the equalize charge procedure described in

Section 14.2.

*IEEE-1188: Recommended Practice for Maintenance,

Testing, and Replacement of Valve-Regulated Lead-Acid

(VRLA) Batteries for Stationary Applications.

CAUTION!

Do not clean plastic parts with solvents,

detergents, oils, mineral spirit or spray

type cleaners as these may cause crazing

or cracking of the plastic materials.