ROC827 Instruction Manual

Issued Mar-06

Input/Output Modules

4-12

Note

: The Discrete Output Relay module operates only with discrete

devices having their own power source.

When a request is made to change the state of a DOR, the request is
immediately sent to the DOR module. There is no scan time associated
with a DOR. Under normal operating conditions, the DOR channel
registers the change within 12 mSecs. If the DOR is in momentary or
toggle mode, DOR channels register the change within 48 mSecs.

The DOR modules draw power for the active circuitry from the backplane.

Note

: On power up or reset, the DO Relay module’s LEDs enter

indeterminate state for a few seconds as the module self-identifies. The
LEDs may flash, stay on, or stay off for a few seconds.

CONTROL

Vs

CONTROL

Vs

EXTERNALLY POWERED

DISCRETE DEVICE

+

-

-

+

SELF- POWERED

DISCRETE DEVICE

-

+

+

-

-

-

-

+

+

+

-

C

H

1

C

H

2

C

H

3

C

H

4

C

H

5

-

Y

DO
RELA

5 CHAN

DOC0509A

R

S

R

S

LATCHING RELAY
NOTE: S = SET

R = RESET

Figure 4-10. Discrete Output Relay Module Field Wiring

Note

: All I/O modules are isolated on the field side. Be aware that you can

induce ground loops by tying commons from various modules together.

4.8

Pulse Input Modules

The Pulse Input (PI) module provides two channels for measuring either a
low speed or high speed pulse signal. The PI module processes signals
from pulse-generating devices and provides a calculated rate or an
accumulated total over a configured period. Supported functions are slow-
counter input, slow rate input, fast counter input, and fast rate input.