EMI Corp User Manual

Page 9

Advertising
background image

www.enviromaster.com

9

Multi-zone Heat Pump Condensing Units

8. Evacuate line to 500 microns or less to

ensure all moisture has been removed

and there are no leaks.

Manifold

Vaccum Pump

Micron Gage

Manifold Setup For Evacuation

S1CA

Shown

It is illegal to discharge refrigerant into

the atmosphere. Use proper reclaiming

methods & equipment when installing or

servicing this unit.

WARNING

!

!

2. Protect the valves by wrapping with a

wet rag "heat sink" before brazing.

1. Clean the ends of tubing and insert into

fi ttings.

7. Attach manifold set.

3. The use of a shield is recommend (one

can be made from some scrap metal)

to protect the paint.

4. Braze tubing into fi ttings.

S1C

Shown

REFRIGERANT PIPING INSTALLATION SECTION

5. Verify that the correct piston for the sys-

tem match is in place, refer to the air

handler Installation Instructions.

6. Refer to the indoor air handler Installa-

tion Instructions for any specifi c details

regarding the connection of tubing.

Connect and braze tubing into the in-

door air handler.