background image

Product Data Document

118DS-16b

July 24, 2007 - Page 2

Bristol

®

Series 9110-00A

Remote Set Regulator

Remote Automation Solutions

Website: www.EmersonProcess.com/Remote

Performance Specifications

Accuracy

Electrical input to pressure output: ±5% of span

Pressure output to feedback: ±5% of span
Feedback volts to pressure output: ±5% of span

Pulse input to pressure output: ±20% of span

Sensitivity

.04% of span (Min. input for readable output)

Repeatability

±0.5% of span

Environmental Effect

±1% max. full scale per 50ºF (28ºC) change

Supply Voltage Effects

±0.15% max. full scale per 1 volt change

Hysteresis Effect

(Output to Gage) ½% of span

Supply Pressure Effect

0.1 Max. PSI change in output for 10 PSI

change in supply pressure (within supply limits)

Gas/Air Consumption

0.007 SCFM at 40 psig supply pressure, at

steady state and increasing supply pressures.

Environmental Specifications

Primary Location

Suitable for field or housed-in unheated

buildings

Temperature Limits

-20 to 150º F (-29 to 66°C) operating
-40 to 185º F (-40 to 85°C) storage

Humidity Limits

10 to 95% RH, -20 to 130° F, (-29 to 55° C)

operating
10 to 50% RH, 130 to 150°F (55 to 66°C)

operating

Vibration Limits

0.1 g max., 10 – 500 Hz

Interference

R.F.I. rejection of the actuator depends on the

shielding of the input and output since the aluminum

housing (with cover in place) greatly attenuates RF

field strength.

Effect with wiring enclosed in conduit SAMA STD

PMC 33.1, Class 1 and 2, 20 MHz to 500 MHz:

<0.5% FS error

Case Classification

Designed to NEMA type 4 hazardous

Safety

Designed to meet ANSI Standard C39.5

Explosion-proof for Class 1, Division 1, Groups B,

C and D; Dust-ignition-proof for Class II, Division 1,

Groups E, F and G; Suitable for Class III, Division 1;

Nonincendive for Class 1, Division 2, Groups A, B,

C and D.