Fig.4, Operation 7. cool air fan 8. maintenance, Troubleshooting – Sealey LP370 User Manual

Page 3

Advertising
background image

IMPORTANT: To ensure continuous ventilation to the heater area, a ventilation opening must connect to the outside of the premises where the heater is to

operate. The opening must be 100cm

2

for every kW of output, and must be set at an equal distance from the upper and lower parts of the heater

operating area.
6.1.

Switching Heater On.

6.1.1. Switch the On/Off switch to the ON (I) position (fig.1.4) and check that the fan starts running.

6.1.2. Push in the gas valve button and hold it in (fig.1.2), at the same time, press (repeatedly) on the Piezo Ignition Button (fig.1.5) until the

flame ignites. When the flame has ignited and the heater has started, keep the gas valve button pushed in for a further 10 seconds, then

release it.

6.1.3. If the heater stops when the gas valve button is released, leave the fan on, wait for one minute, before repeating the ignition

sequence.

Hold the gas valve button in for 15-20 seconds this time, before releasing.

6.1.4. The heat output is controlled by adjusting the gas pressure via the regulator (fig.3). Turn the regulator knob anti-clockwise to reduce the

gas pressure and heat, and clockwise to increase the gas pressure and heat.

6.2.

Switching Heater Off.

6.2.1. After use, shut off the gas cylinder tap. Allow the fan to continue running until the flame shuts down, then switch the On/Off switch to the

OFF (O) position and isolate the heater from the electrical supply.

WARNING! If the flame shuts down during operation, before repeating the ignition sequence, make sure that the fan is not jammed, and

the air inlet and outlet are completely free of obstructions. If it is due to overheating, the cause of the problem must be determined and

corrected before repeating the ignition procedure.

The heater may also be used as a cool air fan, as follows:

7.1.

Remove the gas supply hose and plug the heater into the electrical power supply.

7.2.

Switch on the fan. The unit will now blow out cool air only.

WARNING! Before commencing service or maintenance, disconnect the heater from

the electrical and gas supplies. Use authorised parts only. Unauthorised parts may be

dangerous and will invalidate the warranty. Should the heater require service or

maintenance, a suitably qualified engineer should carry this out or contact your local

Sealey service agent.

8.1.

Check the gas supply hose condition and change if necessary.

8.2.

Carefully clean the fan blade and inside the heater unit with compressed air.

Caution: Wear safety goggles to perform this operation.

8.3.

Check the starting electrode gap (fig.4).

8.4.

Check the ignition unit, safety thermostat, and thermocouple condition and ensure that

they are clean.

WARNING! If for any reason, there is a sudden increase in gas flow (a ruptured supply pipe for instance), the Excess Flow Valve will shut

and cut off the gas supply. Close the tap on the gas cylinder and investigate the problem and resolve it. Re-open the tap on the gas cylinder

and reset the Excess Flow Valve by pressing on the push-button for a few seconds. Carry out the ignition sequence to re-light the heater.

fig.4

6. OPERATION

7. COOL AIR FAN

8. MAINTENANCE

LP370 Issue No: 2(I) - 24/09/14

Original Language Version

© Jack Sealey Limited

PROBLEM

POSSIBLE CAUSE

SOLUTION

The fan motor does not work

1. There is no electrical supply.

2. The motor has locked.

1. Check mains power supply, wire, plug, fuse.

2. Unlock the motor with an appropriate tool.

The ignitor does not spark

1. Electrode has the wrong gap.

2. Faulty connection.

1. Check and reset the electrode to the correct position (fig.4).

2. Check and connect correctly the ignitor and the electrode.

No gas flow to the burner

1. The cylinder gas tap is closed.

2. The cylinder is empty.

3. Gas leaks from the supply.

1. Open the gas tap.

2. Replace the cylinder.

3. Remove and clean the nozzle, check for leaks by using a

foamy soap only - DO NOT USE A FLAME to find a leak.

The burner starts, but it stops as

the gas valve is released.

1. The thermocouple is not warm enough.

2. The safety override has activated

because the fan does not work.

1. Repeat the starting operation, keeping the button pushed for

a slightly longer time.

2. See above “Fan motor does not work”.

The heater stops during operation 1. Excessive gas supply.

2. Insufficient air flow.

3. Insufficient gas due to ice formation

on the cylinder.

4. Excess flow valve has shut.

1. Check the pressure regulator, and replace if necessary.

2. Check that the motor is working correctly.

3. Check and if necessary use a larger gas cylinder or multiple

cylinders connected in parallel.

4. Investigate and rectify fault, reset valve before restarting.

9. TROUBLESHOOTING

WARNING! Regarding Air Contaminants.

Air contaminants taken into the heater will damage the unit, cause health problems and safety issues.

Example: Body shop filler dust and overspray dust will clog the burner diffuser, contaminate the combustion chamber and damage the

internal parts of the heater. If contaminants are present the heater must be supplied with ducted clean air.

Please note that any parts damaged by filler dust or overspray dust will not be covered by warranty. Additionally a cleaning

charge will be made for any heaters damaged by filler dust or overspray dust.