10. TROUBLE SHOOTING

10-1 NO AC OUTPUT

10-1-1 CHECKING STATOR

■ Remove control panel and disconnect black,

blue, red, and white wires at the connectors.

■ Measure the resistance between terminals on

stator leads.
Refer to the table below for normal resistance, If
stator is faulty, replace with a new one.

10-1-2 CHECKING CONDENSER

■ If an instrument (QC-meter or C-meter) for mea-

suring capacity of condenser is available, check
the capacity of condenser.

■ If such an instrument is unavailable, the condenser can be checked by replacing with a new one. If the

generator performs good with new condenser, the cause of trouble is defect in original condenser.

10-1-3 CHECKING OF ROTOR

(1)

CHECKING FIELD COIL

■ Remove rear cover and stator.
■ Unsolder the coil ends from the terminals on the

rotor.

NORMAL CAPACITY OF CONDENSER

MODEL

RGD3300H

RGD5000H

60 Hz

60 Hz

CONDENSER

20 µF

30 µF

20 µF

30 µF

CONDENSER

1

2