JOHNSON CONTROLS

20

FORM 145.32-IOM1 (908)

Flash code number corresponds to a number of LED

flashes, followed by a pause and then repeated.

TRIP and ALERT LED’s flashing at the same time

means control circuit voltage is too low for opera-

tion.

Resetting Alert Codes

Alert codes can be reset manually and automatically.

The manual method to reset an Alert code is to cycle the

power to Comfort Alert off and on. For automatic reset,

Comfort Alert continues to monitor the compressor and

system after an Alert is detected. If conditions return to

normal, the Alert code is turned off automatically. ALERT

codes that result in a compressor lock out can only be

reset manually. ALERT codes that result in a lockout

can only be reset manually.

Status LED

Status LED Description

Status LED Troubleshooting Information

1. Low line voltage to compressor

2. Excessive liquid refrigerant in compressor

3. Compressor bearings are seized

1. Condensing unit power disconnect is open

2. Compressor circuit breaker or fuses are open

3. Compressor contactor has failed open

4. High pressure switch is open and requires manual reset

5. Broken supply wires or connector is not making contact

6. Unusually long compressor protector reset time due to

extreme ambient temperature
7. Compressor windings are damaged

1. Compressor fuse is open on one phase

2. Broken wire or connector on one phase

3. Compressor motor winding is damaged

4. Utility supply has dropped one phase

Yellow “ALERT”

Flash Code 7

Reverse Phase

LOCKOUT

1. Compressor running backward due to

supply phase reversal
1. Compressor contactor has failed closed

2. Thermostat demand signal not connected to module

1. Control circuit transformer is overloaded

2. Low line voltage to compressor

Yellow “ALERT”

Flash Code 9

Low Voltage

Control circuit < 18VAC

Yellow “ALERT”

Flash Code 5

Open Circuit

Yellow “ALERT”

Flash Code 8

Welded Contactor

Compressor always runs

Yellow “ALERT”

Flash Code 6

Missing Phase

LOCKOUT

Locked Rotor

LOCKOUT

Yellow “ALERT”

Flash Code 4

Advertising