7. SPECIFICATIONS

7.1.

European directives

This instrument has been designed in compliance with the EMC standards in force and its
compatibility has been tested for EN50081-1 (class B) and EN50082-2.
This instrument complies with the prescriptions of the European directive on low voltage
73/23/CEE (LVD) and EMC directive 89/336/EEC, amended by 93/68/EEC.


7.2.

Safety Standards

Standard:

EN61010-1, EN61010-2-032

Insulation:

Double insulation

Pollution:

2

Working category:

CAT III, 1000 V AC

RMS

Phase - Earth



7.3.

Electrical features

Current Range:

3000A AC

RMS

Output Sensitivity (on 10k

):

39.1uV/A

Accuracy (at +25°C):

1.5% of reading (45 - 65Hz)

Frequency Range:

from 10 Hz to 5kHz (-3dB)

Phase Error:

< ± 1° (Output on 10k

2mV, 45 - 65 Hz)

< ± 3° (Output on 10k

< 2mV, 45 - 65 Hz)

Position Sensitivity:

2 % of range conductor close to coil

4 % of range close to coil fastener



7.4.

Measuring head mechanical features

Length of transducer:

0.60m

Maximum conductor diameter:

approx. 7" (180 mm)

Bend radius:

38mm

Output Connection:

approx. 2.0m cable with 3 way connector

Weight:

215 g



7.5.

Environment

Operating Temperature:

from -20°C to +60°C

Storage Temperature:

from -40°C to +80°C

Operating and storage humidity:

from R

H

15 % to R

H

85 %