Specifications

Note: Part Numbers GXT2-6000RT208 and GXT2-10000RT208 do not include internal battery kits. When calculating total unit weight, add weight of internal batteries.

LIEBERT GXT2 6 KVA

LIEBERT GXT2 10 KVA

Model Number

GXT2-6000RT208

GXT2-10000RT208

Model Rating

4200W/5200VA at 127/220 (120 or 240 degrees)

8000W/8660VA at 127/220 (120 or 240 degrees)

4200W/5200VA at 120/208 (120 or 240 degrees)

8000W/8660VA at 120/208 (120 or 240 degrees)

4200W/6000VA at 120/240 (180 degrees)

8000W/10000VA at 120/240 (180 degrees)

4200W/6000VA at 115/230 (180 degrees)

8000W/10000VA at 115/230 (180 degrees)

3780W/5400VA at 110/220 (180 degrees)

7200W/9000VA at 110/220 (180 degrees)

3360W/4800VA at 100/200 (180 degrees)

6400W/8000VA at 100/200 (180 degrees)

DIMENSIONS Unit W x D x H in. (mm)

6.9 x 24.2 x 16.9 (176 x 615 x 430)

10.5 x 26.0 x 16.9 (267 x 660 x 430)

WEIGHT lbs (kg) Unit

67 (30.3)

109 (49.3)

INPUT AC PARAMETERS
Nominal Operating Frequency

50 or 60 Hz (Factory Default = 60)

Factory Default VAC

120/208 VAC at 120 degrees

L1-L2 Factory Default Input Phase Angle

120 degrees

Allowable Input Phase Angle

120, 180, 240 degrees, Auto-sensing on application of AC (Restrictions for L-N voltages other than 120 VAC)

Factory Default L1-N, L2-N VAC

120 VAC nominal

Input Frequency w/o Battery Operation

40 - 70 Hz

OUTPUT AC PARAMETERS
Factory Default VAC

120/208 VAC @ 120 degrees

L1-L2 Factory Default Output Phase Angle

120 degrees

Allowable Output Phase Angle

120, 180, 240 degrees Auto-sensing on initial application of input AC

Factory Default L1-N, L2-N VAC

120 VAC nominal

User Configurable L1-N, L2-N VAC

100/110/115/120/127 VAC, ±3%

Frequency

50 Hz or 60 Hz, Nominal

Waveform

Sinewave

Overload Rating

200% for 8 cycles; 130% for 10 seconds

200% for 8 cycles then shutdown; 130% for 60 seconds

with transfer to bypass

with transfer to bypass

ENVIRONMENTAL
Operating Temp

+32°F to +104°F (0°C to +40°C)

Storage Temp

+5°F to +122°F (-15°C to +50°C)

Relative Humidity

0% to 95%, non-condensing

Operating Elevation

Up to 10,000 ft. (3000m) at 104°F (40°C) without derating

Storage Elevation

50,000 ft. (15,000 m) maximum

Audible Noise

<55 dBA, at 1 meter from the rear; <50 dBA, at 1 meter from the front or sides

AGENCY
Safety

UL 1778, c-UL Listed (Suitable for computer room applications)

RFI/EMI

FCC Part 15, Subpart B, Class A

Surge Immunity

IEEE/ANSI C62.41 Category A & B

Transportation

ISTA Procedure 1A

INTERNAL BATTERY
Model Number

GXT2-144BATKIT (one required)

GXT2-288RTBKIT (two required)

WEIGHT lbs (kg)

79 (35.8) (one required)

78.1 (35.5) (two required)

Type

Valve-regulated, non-spillable, flame retardant, lead acid

Quantity x V x Rating

12 x 12V x 9.0 AH (one required)

12 x 12V x 9.0 AH (two required)

Battery Mfg / Part #

Yuasa / REW 45-12 FR

Recharge Time

6 Hours to 90% capacity after full discharge into 100% load

OPTIONAL EXTENDED BATTERY CABINET
Model Number

GXT2-144VBATT

GXT2-288RTVBATT (requires two GXT2-288RTBKIT)

DIMENSIONS W x D x H in.(mm)

3.5 x 24.2 x 16.9 (87 x 618 x 430)

7.0 x 26.0 x 16.9 (178 x 660 x 430)

WEIGHT lbs (kg) Unit

93.6 (42.5)

197.8 (89.9) (Total weight with batteries)

BATTERY PARAMETERS
Type

Valve-regulated, non-spillable, flame retardant, lead acid

Qty x V x Rating

12 x 12V x 9.0 AH per kit

12 x 12V x 9.0 AH per kit (two required)

Battery Mfg / Part #

Yuasa / REW 45-12 FR

ENVIRONMENTAL
Operating Temp

+32°F to +104°F (0°C to +40°C)

Storage Temp

+5°F to +122°F (-15°C to +50°C)

Relative Humidity

0% to 95%, non-condensing

Operating Elevation

Up to 10,000 ft. (3000m) at 104°F (40°C) without derating

Storage Elevation

50,000 ft. (15,000m) maximum

AGENCY
Safety

UL 1778, c-UL Listed (Suitable for computer room applications)

RFI/EMI

FCC Part 15, Subpart B, Class A

Transportation

ISTA Procedure 1A

168997_SL23172:15615 govern 7/22/08 2:30 PM Page 15