The OpenComms EM must be installed indoors where electrical service is available. The unit should be

placed where it can be easily accessed for making connections. It may be placed on a flat surface or

mounted on a wall (see the user manual for mounting instructions). Consider the length of the sensor and

other cables and the distance to the monitored area when deciding where to place the unit.
Refer to Figure 1 when making the connections in Steps 1 - 5 below to the ports on the back of the

OpenComms EM. The port placement and port labels differ for each model.

Figure 1

Rear view - OpenComms EM ports

MAKE THESE CONNECTIONS:

After connecting,

check indicators

on front of unit:

1. POWER: Connect the DC power adapter to the DCN/Power port on the back of the

OpenComms EM.

Power

ON (red)

2. ETHERNET: Connect a straight-through CAT5 Ethernet cable from your 10 Mbit

network to the Ethernet/ETH port on the back of the OpenComms EM.

Link/Cx

ON (green)

3. MODEM: If using a modem, connect an RJ45 cable from a modem to the Modem

port on the back of the unit (see the user manual for modem

setup and pinout).

Activity/Modem/

Mdm

ON (green)

4. SENSOR: Use a sensor—temperature, humidity, combination temperature &

humidity or water detection—or a contact closure cable.*
Connect a sensor or contact closure cable to any sensor port (e.g., Sensor 1,

Sensor 2). These connections may be made in any order; the ports are identical

and are configured to accept and recognize all types of sensors.

Sensor 1-2

(EM/EM PDU)

or

Sensor 1-4

(vEM-14)

ON (green)

5. SERIAL (EM PDU Controller only): Use the serial cable provided with EM PDU

controllers (available separately for vEM-14 controllers).*
Connect the six-wire end of the serial cable into the RS232 port of an MP

Advanced power strip.
Connect the other end (eight-wire) of the serial cable to either serial port (Serial 1

or Serial 2) of the OpenComms EM.

Serial 1

or

Serial 2

ON (green)

* See the user manual for instructions on making your own cable. (For a contact closure cable, the orange/white and white/orange wires must

be tied together to form the common. The blue/white wire is the contact that may be defined as either Normally Open or Normally Closed.)

EM

CONTROLLER

Rear of unit

Sensor

2

Sensor

1

Modem DCN

Ethernet

Power

Sensors

Modem

Sensor

2

Sensor

1

Serial

2

Serial

1

Modem

DCN Ethernet

Power

Serial

devices Ethernet

Sensors

Modem

Serial

devices Ethernet

EM PDU

CONTROLLER

Rear of unit

vEM-14

CONTROLLER

Rear of unit

Power

Dry

contact

inputs

Built-in

temperature

& humidity

sensor

Advertising