ProSoft Technology ILX69-PBS User Manual
Page 69
Advertising

ILX69-PBS ♦ CompactLogix or MicroLogix Platform
Contents
PROFIBUS Slave Communication Module
User Manual
ProSoft Technology, Inc.
Page 69 of 102
March 20, 2015
CIP
Status
Extende
d
Status
Meaning
Cause
Help
FE hex
0000 hex
Message Timeout
No answer message was
received.
FF hex
0514 hex
General Error
Non-specified error
occurred
Call support
FF hex
0517 hex
General Error
Unknown command /
Invalid Parameter
The values in Requested
Command is unknown or the
parameter of the requested
command are invalid
The value Req.Command must
be initialized, For Read/Write
Response request check if you
answer with proper Slot, Index
etc. from Dpv1StatusRegister
Advertising