ProSoft Technology MVI69-GSC User Manual
Page 54

Ladder Logic
MVI69-GSC ♦ CompactLogix or MicroLogix Platform
User Manual
Generic ASCII Serial Communication Module
Page 54 of 102
ProSoft Technology, Inc.
September 24, 2010
4 Click [+] to expand the .CONFIG.M
OD
D
EF
section, and then change the
R
EAD
R
EG
C
NT
parameter from 600 to 1000.
5 To modify the WriteData
array, follow the above steps, substituting WriteData
for ReadData. Also, make sure that the ReadData
and WriteData
arrays do
not overlap in the module memory. For example, if your application requires
2000 words of WriteData starting at register 0, then your Read Register Start
parameter must be set to a value of 2000 or greater in ProSoft Configuration
Builder.
6 Save and download the sample configuration.
It is unnecessary to manually edit the ReadData and WriteData user-defined
data types in the ladder logic, as these are automatically updated to match
the changed array sizes in ProSoft Configuration Builder.