Rs-485 application port(s), Rs-485 and rs-422 tip, Db9 to rj45 adaptor (cable 14) – ProSoft Technology PC56-OPC User Manual
Page 25

Reference PC56
♦ ControlLogix Platform
User Manual
In-Rack Industrial PC
ProSoft Technology, Inc.
Page 25 of 34
November 18, 2009
6.2.4 RS-485
Application
Port(s)
The RS-485 interface requires a single two or three wire cable. The Common
connection is optional and dependent on the RS-485 network. The cable required
for this interface is shown below:
Note: Terminating resistors are generally not required on the RS-485 network, unless you are
experiencing communication problems that can be attributed to signal echoes or reflections. In this
case, install a 120-ohm terminating resistor on the RS-485 line.
RS-485 and RS-422 Tip
If communication in the RS-422/RS-485 mode does not work at first, despite all
attempts, try switching termination polarities. Some manufacturers interpret +/-
and A/B polarities differently.
6.2.5 DB9 to RJ45 Adaptor (Cable 14)