3.1.16 CfgErrword (Configuration/Error Status Flags)
The CfgErrword member reports configuration errors for the respective server. If
the module is not functioning as expected, inspect the value presented in this
object. If a configuration error exists, the associated bit will be set. A value of
zero for the bit indicates the configuration value is valid. This does not guarantee
that the module is configured correctly for your application. The bits used by this
member are shown below:
Bit Position
Description
Bit 0
0x01
A value other than Yes or No was entered for the enabled
parameter.
Bit 1
0x02
Not used.
Bit 2
0x04
A value less than 5000 but not 0 is entered for the timeout
parameter.
Bit 3
0x08
An invalid value is entered for the Connection Close Type
parameter. The program only accepts a value of 0 to 2.