BACnet Protocol Configuration

BACnet ♦ ProLinx Gateway

Protocol Manual

BACnet/IP Client Edition 2

Page 26 of 52

ProSoft Technology, Inc.

November 24, 2010

3.3

BACnet Client 0 Commands

The BACnet Client 0 Commands section defines the BACnet commands to be

issued for data collection and control of the remote units on the UDP/IP network.

The gateway supports numerous commands to interface with many different

units and data types. For the commands to operate correctly, the server device

must be configured correctly. An incorrectly configured server is the primary

cause of user problems with the gateway.

3.3.1 Command List Overview

In order to interface the ProLinx gateway with BACnet Server devices, you must

construct a command list. The commands in the list specify the server device to

be addressed, the function to be performed (read or write), the data area in the

device to interface with, and the registers in the internal database to be

associated with the device data.
Up to 100 commands can be entered in the command list for the Client port. The

command list is processed from top (command #1) to bottom. A Poll Interval

parameter is associated with each command to specify a minimum delay time in

tenths of a second between issuances of the command. If the user specifies a

value of 10 for the parameter, the command will be executed no more frequently

than every one (1) second.