ProSoft Technology BM-1000-PM1K User Manual
Page 32

Diagnostics
Page 32 of 36
ProSoft Technology, Inc.
June 10, 2015
2. I/O LED (Right):
a. Green: USB enabled
b. LED not on: No power
i.
Connect USB to PC first, then to I/O Expansion Module.
ii.
Verify unit is powered on, Power LED (left) should be red.
iii.
Verify the PC is on.
3. Unable to Read/Write Modbus Values
a. Verify that the Modbus slave ID is the Module ID + 1
Example: If the Module ID is 0, the Modbus slave ID will be 1
b. Select MSB first when applicable when setting up Modbus Master device.
c. Verify Modbus RS485 wiring (3-wire).
d. Verify baud rate, data bits, parity, and stop bits (9600 / 8 / None / 1).
e. Refer to Modbus Mapping (page 27).
i.
Verify the Modbus function code.
ii.
Verify the Modbus register address.
iii.
Verify the data type (integer/float, 16/32 bit).
iv.
Verify if address has read/write or only read function capabilities.