3 master command status, 1 master command status error code definitions – ProSoft Technology 5301-MBP-ASCII User Manual

Page 38

Advertising
background image

Serial Port Modbus Error and Status Data

MBP ♦ ProLinx Gateway

Protocol Manual

Modbus Plus

Page 38 of 52

ProSoft Technology, Inc.

May 12, 2011

6.3

Master Command Status

The following table lists the registers that contain Master Command Status error
codes for each device. The register address range is 4170 to 4369.

Status Register

Description

4170

Master Command Status: #1

4171

Master Command Status: #2

4172

Master Command Status: #3

4173

Master Command Status: #4

4174

Master Command Status: #5

-

----

4368

Master Command Status: #199

4369

Master Command Status: #200

6.3.1 Master Command Status Error Code Definitions

The following error codes may be present in the Master Command Status error
code registers listed in the previous table. The following table lists each of the
codes and associated definition.

High Byte

Low Byte

Description

0x00

Normal: Driver will reset when processing commands.

0x01

Command has completed successfully.

0x02

Routing Errors

0x01

No response received: Is addressed unit online?

0x02

Program access denied.

0x04

Exception response received.

0x08

Invalid node type in routing path.

0x10

Slave rejected the Modbus command: Invalid input path?

0x20

Initiated transaction forgotten by slave.

0x40

Unexpected master output path received.

0x80

Unexpected response received.

0x04

Configuration Errors

0x01

Invalid configuration for command.

0x02

Invalid command type: 1=Write, 2=Read, All other errors.

0x04

0x08

0x10

0x20

0x40

0x80