32

ENVISION CONSOLE INSTALLATION MANUAL

ECM2 Blower Operation

Fan speeds will be selected through the user interface or
the facility management system. There will be a total of 12
speeds selectable with only three being selected at any
one time. The lowest numbered speed selection set to ON
will select the low-speed fan setting, the middle selection
set to ON will select the medium-speed fan setting and
the highest selection set to ON will select the high-speed
fan setting. If all selections are set to OFF the software
shall select speed setting 10 for low-speed, 11 for medium-
speed, and will select speed setting 12 for high speed. If
only one selection is set to ON, that selection will set the
low-speed fan setting, the medium-speed setting will be 11,
and the high-speed setting will be speed 12. The maximum
low-speed setting will be speed 10 and the minimum high-
speed setting will be speed 3. In addition there is a low limit
setting in the software to prevent the ECM2 fan speed from
being set below acceptable limits for each unit size.

ECM2 Fan air flow “Soft Switch Settings”

A set of 12 “soft switches” accessible through the user
interface or building automation system are used to select
the three fan speed settings for the ECM2 fan motor.
The 12 soft switches work in exactly the same way as the
hardware switches used on the Premier control (Refer to
Fan Performance Data - ECM2 Motor for proper settings).
No more than three soft switches may be set to the “ON”
position. The first “ON” switch (the lowest number switch)
determines the “low speed fan” setting. The second de-
termines the “medium speed fan” setting, and the third
determines the “high speed fan” setting.

Emergency Heat/Network Enabled Output (BO5)

This output is set from the factory to enable/disable
emergency heat. If a problem occurs with the unit result-
ing in the compressor being locked out in heating mode,
the control will automatically enable this output to turn
on field installed electric heat. This output is interlocked
with the fan proving input BI-6 (Fan proving sensors must
be field supplied and installed). BI-6 must be connected
to PB2 position 3 (see unit schematic) in the field if no fan
proving sensor is desired. There is a configurable parame-
ter available through a BAS network that must be enabled
if this output is to be commanded over the BAS network.

MUI Alarm History Reporting

If a fault occurs the fault will be recorded in history for
display on the medium user interface in the History Menu.
Each fault type will be displayed in the history menu with
a number between 0 and 3. A reading of 3+ will mean
that fault has occurred more than three times in the past.
The history menu can be cleared with a power cycle only.
Alarm date and time are not included in the history.

Inputs & Outputs Configuration

Field Selectable Options

Water Coil Low Temp (Freeze Sensing) Limit Set Point (BI-5)
The water coil low temperature (freeze sensing) limit set
point input allows you to adjust the water coil low tem-
perature (freeze sensing) limit set point (AI-5). When the
jumper is installed on BI-5 (Wire #24) the water coil low
temperature (freeze sensing) limit set point is factory set
for 30°F. When the jumper on BI-5 (Wire #24) is removed
the water coil low temperature (freeze sensing) limit set
point will be 15°F.

Accessory Outputs (BO-7 and BO-8)
Accessory Output 1 will be energized 90 seconds prior to
the compressor output being energized. Accessory Output
2 will be energized with the fan output (BO-1). When the
corresponding compressor output is turned off the acces-
sory output will be deactivated immediately. These outputs
are selectable for normally open or normally closed opera-
tion through the Medium User interface or through the
Building Automation System.

Control Accessories

Zone Sensors

TAXXJ02 Room Command Module

TAXXA01 LCD Room Command Module

A99 Sensor

MUI (LCD User interface) for diagnostics
and commissioning.

MUIK1 - Panel Mount, Portable

MUIK2 - Wall Mount

Envision Console Controls

Input Name

Input Output Name

Output

Zone Temp 1

AI 1 Fan Enable

BO1

Relative Humidity Input

AI 2 Comp – Low Capacity

BO2

Condensate Level

AI 3 Reversing Valve

BO3

Universal Temp Input

AI 4 Comp – Full Capacity

BO4

Water Coil Low Temperature Limit

AI 5 Network Output/EH Output

BO5

Warm/Cool Adjust and Temp Occ

AI 6 Alarm

BO6

Accessory 1 Output

BO7

Occupied

BI 1 Accessory 2 Output

BO8

Emergency Shutdown

BI 2 Network Controlled Output

B09

Stage 1 Low Pressure

BI 3

Network Viewable Input 1

BI 4 ECM2 Fan

PWM1

Water Coil Low Temp Limit Set Point

BI 5 Network Controlled Output

PWM2

Network Viewable Input 2

BI 6

Thermostat Y1

BI 7

Thermostat Y2

BI 8

Thermostat O

BI 9

Thermostat G

B10

Stage 1 High Pressure

BI11

Compressor Proving

BI12

XP10 Expansion Card
Input Name

Input Output Name

Output

Unused

AI 1 Unused

BO 1

Unused

AI 2 Unused

BO 2

Unused

AI 3 Unused

BO 3

Unused

AI 4 Unused

BO 4

SINGLE and DUAL STAGE WATER-TO-AIR