Technical specifications, For model with 3 phase in 1 phase out, For tower model – EMC 4K VA 20K VA UPS User Manual

Page 17

Advertising
background image

28

9. Technical Specifications


For model with 3 Phase in 1 Phase out

Tower model (with LCD display)

8K31

10K31

12K31

15K31

20K31

Capacity (VA)

8000VA

10000VA

12000VA

15000VA

20000VA

Capacity

Capacity (W)

5600W

7000W

8400W

10500W

14000W

208/360V, 220/380V, 230/400V, 240/415V(3Ф5W)

Load Capacity

Voltage/Range

Load Capacity

208~241V

0~25%

242~276V

0~40%

Voltage/Load

277~311V

0~75%

312~478V

0~100%

Input

Frequency

50/60 Hz Auto Sensing

Voltage (on battery)

100V, 110V, 115V, 120V / 208V, 220V, 230V, 240V +/-2% (Selectable Output Voltage)

Frequency (on battery)

50 / 60 Hz +/-0.5%

Transfer Time

0 ms

Overload Recovery

Auto transfer to UPS

High Efficiency mode

(AC to AC)

> 97 %

UPS Design

Technology

On-Line / Fully digitized microprocessor controlled

Output Wave Form

Sine wave

Harmonic distortion

< 3% of T.H.D. at linear load

Output

Crest Factor

3 : 1

Surge Protection

IEC61000-4-5 level 3

Overload Protection

125% for 1 minutes and 150% for 10 seconds 130% for 10 seconds and 150% for 1.5

seconds (On-battery)

Protection

and Filtering

Short Circuit Protection

UPS output cut off immediately or input fuse / circuit breaker protection

Visual Display (LED

model)

UPS on(green), line-mode(green), battery mode(yellow), bypass(yellow), fault(red)

Visual Display (LCD

model)

Input / output voltage, input / output frequency, on-line mode, back up mode, battery

capacity, load level

Audible Alarm (Battery

back-up)

Beep every 5 sec

UPS Fault

Continuous beeping sound and LCD display

System

Display/

Warning

Communication

RS-232 Serial Port and USB

Type

Sealed, maintenance-free lead acid batteries

DC Voltage (V) Battery

(Tower )

240V /

12V7.2AH x

20

240V /

12V9AH x 20

240V /

12V7.2AH x 20 x

2SET

240V /

12V7.2AH x

20 x 2SET

240V /

12V9AH x 20

x 2SET

Typical Recharge Time

to 90% Full

4 hours

Management

Self-test, adjustable battery transfer points and alarm settings

Battery Protection

Cut off without draining any current when battery is low

Cold Start (DC start)

YES

Battery

Back Up Time (Tower

model)

About 4~6 min Full load / 10~15min Half load

Input Inlet

Hardwire

Receptacles

Hardwire

Dimensions W x D x H

mm (inch) W/O ISOTR

257 x 690 x 715

(10.1" x 27.2" x 28.1")

342 x 690 x 878

(13.5"x27.2"x34.6")

342 x 863 x 905

(13.5" x 34.0" x 35.6")

Net Weight kg (lb) W/O

ISOTR

80.0 (176.0)

176.5 (388.3)

175.0 (385.0)

Shipping Weight kg (lb)

W/O ISOTR

101.5 (223.3)

206.5 (454.3)

196.0 (432.3)

Dimensions W x D x

H mm (inch) W/

ISOTR

342 x 690 x 715

(13.4" x 27.2" x 28.1")

342 x 690 x 878

(13.5"x27.2"x34.6")

342 x 863 x 905

(13.5" x 34.0" x 35.6")

Physical

Net Weight kg (lb)

W/ ISOTR

130.0 (286.0)

176.5 (388.3)

225.0 (495.0)

29

Shipping Weight kg

(lb) W/ ISOTR

151.5 (333.3)

206.5 (454.3)

246.5 (542.3)

Operating

Temperature

0~40°C / 32~104°F

Storage

Temperature

-20~50°C / -4~122°F

Altitude

3,500 meters max

Audible Noise (1

meter from surface)

< 55 dB

Environment

Relative Humidity

0 ~ 95% humidity, non-condensing


For Tower model

Tower model (with LCD display)

VGD-4000

VGD5000

VGD-6000

VGD-8000

Capacity (VA)

4000VA

5000VA

6000VA

8000VA

Capacity

Capacity (W)

2800W

3500W

4200W

5600W

Voltage (on battery)

208V, 220V, 230V, 240V +/-2% (Selectable Output Voltage) For 4K / 5K / 6K

100V, 110V, 115V, 120V / 208V, 220V, 230V, 240V +/-2% (Selectable Output Voltage)

For 6K / 8K with output isolation transformer

Frequency (on

battery)

50 / 60 Hz +/-0.5%

Transfer Time

0 ms

Overload Recovery

Auto transfer to UPS

High Efficiency

mode (AC to AC)

> 95 %

> 97 %

UPS Design

Technology

On-Line / Fully digitized microprocessor controlled

Output Wave Form

Sine wave

Harmonic distortion

< 3% of T.H.D. at linear load

Output

Crest Factor

3 : 1

Surge Protection

IEC61000-4-5 level 3

Overload

Protection

125% for 1 minutes and 150% for 10 seconds (On-line) 130% for 10 seconds and 150%

for 1.5 seconds (On-battery)

Protection and

Filtering

Short Circuit

Protection

UPS output cut off immediately or input fuse / circuit breaker protection

Visual Display

(LED model)

UPS on(green), line-mode(green), battery mode(yellow), bypass(yellow), fault(red)

Visual Display

(LCD model)

Input / output voltage, input / output frequency, on-line mode, back up mode, battery

capacity, load level

Audible Alarm

(Battery back-up)

Beep every 5 sec

UPS Fault

Continuous beeping sound and LCD display

System/Display

/Warning

Communication

RS-232 Serial Port and USB

Type

Sealed, maintenance-free lead acid batteries

DC Voltage (V)

Battery (Tower )

120V / 12V7AH

x 10

120V / 12V9AH

x 10

240V / 12V7.2AH

x 20

240V / 12V7.2AH

x 20

Typical Recharge

Time to 90% Full

4 hours

Management

Self-test, adjustable battery transfer points and alarm settings

Battery Protection

Cut off without draining any current when battery is low

Cold Start (DC

start)

YES

Battery

Back Up Time

(Tower model)

4 min. Full load /

10 min. Half load

5 min. Full load /

13 min. Half load

About 4~6 min Full load / 10~15min Half load

Input Inlet

Hardwire

Receptacles

IEC C13*8 ; C19*2

Hardwire

Physical

Dimensions W x D

x H mm (inch) W/O

ISOTR

257*537*440

(10.1”x21.1”x17.3”)

257 x 590 x 570

(10.1"x23.2"x22.4")

257 x 690 x 715

(10.1" x 27.2" x

28.1")