16941-5-0907

Page 5

*Floor stand can not be used in a bedroom installation. SR-10T must be wall mounted in a bedroom installation.
The bathroom or bedroom must be an unconfined space. ANSI Z223.1/NFPA54 defines an unconfined space as “a space whose volume is

not less than 50 cubic feet per 1,000 Btu per hour (4.8m

3

per kw) of the aggregate input rating of all appliances installed in that space.”

Instructions to Installer

1. Installer must leave instruction manual with owner after

installation.

2. Installer must have owner fill out and mail warranty card supplied

with unvented room heater.

3. Installer should show owner how to start and operate unvented

room heater.

Always consult your local Building Department regarding

regulations, codes or ordinances which apply to the installation of

an unvented room heater.
This appliance may be installed in an aftermarket* permanently

located, manufactured (mobile) home, where not prohibited by

state or local codes.
*Aftermarket: Completion of sale, not for purpose of resale, from

the manufacturer.

This appliance is only for use with the type of gas indicated on the

rating plate. This appliance is not convertible for use with other

gases.
General Information

This appliance is design certified in accordance with American

National Standards Institute Z21.11.2 by the Canadian Standards

Association Laboratories as an Unvented Room Heater and shall

be installed according to these instructions.
Any alteration of the original design, installed other than as

shown in these instructions or use with a type of gas not shown on

the rating plate is the responsibility of the person and company

making the change.
Important

All correspondence should refer to complete Model Number, Serial

Number and type of gas.
Well Head Gas Installations

Some natural gas utilities use “well head” gas. This may affect the

Btu output of the unit. Contact the gas company for the heating

value. Contact the manufacturer or your gas company before

changing spud/orifice size.
Qualified Installing Agency

Installation and replacement of gas piping, gas utilization equipment

or accessories and repair and servicing of equipment shall be

performed only by a qualified agency. The term “qualified agency”

means any individual, firm, corporation, or company that either in

person or through a representative is engaged in and is responsible

for (a) the installation, testing, or replacement of gas piping or (b) the

connection, installation, testing, repair, or servicing of equipment;

that is experienced in such work; that is familiar with all precautions

required, and that has complied with all the requirements of the

authority having jurisdiction.

State of Massachusetts: The installation must be made by

a licensed plumber or gas fitter in the Commonwealth of

Massachusetts.
Sellers of unvented propane or natural gas-fired supplemental

room heaters shall provide to each purchaser a copy of 527 CMR

30 upon sale of the unit.
In the State of Massachusetts, unvented propane and natural

gas-fired space heaters shall be prohibited in bedrooms and

bathrooms.

The installation must conform with local codes or, in the absence

of local codes, with the National Fuel Gas Code, ANSI Z223.1

(latest edition).*

*Available from the American National Standards Institute, Inc.,

11 West 42nd St., New York, N.Y. 10036.
High Altitudes

For altitudes/elevations above 2,000 feet (610m) ratings should be

reduced at the rate of 4 percent for each 1,000 feet (305m) above

sea level. Contact the manufacturer or your gas company before

changing spud/orifice size.

INTRODUCTION

SPECIFICATIONS

Model

SR-10T

SR-18T

SR-30T

Input BTU/HR (KW/H) Five Plaques

-

-

30,000 (8.8)

BTU/HR (KW/H) Three Plaques

-

18,000 (5.3)

-

BTU/HR (KW/H) One Plaque

10,000 (2.9)

-

-

Height

22” (559mm)

22” (559mm)

22” (559mm)

Width

11 7/8” (302mm)

18” (457mm)

24 1/8” (613mm)

Depth

6 1/2” (165mm)

6 1/2” (165mm)

6 1/2” (165mm)

Gas Inlet

3/8” (10mm)

3/8” (10mm)

3/8” (10mm)

Accessories
Blower

-

SRB-18T

SRB-30T

Floor Stand

SRS-10*

SRS-18

SRS-30