Initial installation – Enviro EG28-120 User Manual

Page 20

Advertising
background image

Figure 23: Vent restrictor ring.

Figure 22. Possible Vent Configurations; Vertical

and Horizontal Terminations.

V

ENT

C

ONFIGURATIONS

:

Figures 22 shows the range of venting options, it

shows possible vent configurations if the unit is top

vented, for vertical and horizontal terminations,

any layout that remains within the shaded area is

acceptable. Having the fewest number of elbows is

ideal, as they tend to disrupt air movement. Using

45˚ elbows is preferable to using 90˚ elbows. Also, a

shorter vent system will perform better than a longer

one.
NOTE: The total length of the vent pipes can not

exceed 33 feet (10.1 m). Any combination of rise and

run can be used as long as it lays within the shaded

area (a total of three (3) 90° elbows or six (6) 45°

elbows can be used). In addition to what is shown, if a

90° elbow is used in the horizontal plane, 3 feet (91.4

cm) must be subtracted from the allowable horizontal

run (for each 45° elbow, 11⁄2 feet must be subtracted

from the allowable horizontal run).

V

ENT

R

ESTRICTOR

R

ING

:

A vent restrictor ring is supplied with each direct vent fireplace.

This restrictor ring is to be installed when the vertical chimney

installation is over 15 feet (4.57 m). Before the chimney is

placed onto the stove, place this vent restrictor ring into the 4

inch (10.2 cm) flue pipe (as shown), once the vent restrictor

ring has been installed, the vertical sections of chimney can be

installed.

V

ENT

C

ONFIGURATIONS

:

Initial Installation

QUALIFIED INSTALLERS ONLY

20