Operator Control and Display Panel

68

Settings

Display contrast

Adjust the LCD display contrast

Date format set

Choose the format for date display: M/D/Y, D/M/Y, M/D/Y, Y/M/D

Date & time

Set the date and time

Comm1 baud rate

Communication baud rate setting for Intellislot 1

Comm2 baud rate

Communication baud rate setting for Intellislot 2

Comm3 baud rate

Communication baud rate setting for Intellislot 3

Communication address

This setting is applicable to RS485 communication mode

Communication mode

Communication Mode Setting

Callback times

When Intellislot 1 Communication mode is Modem, this parameter sets the

number of times a number is redialed to send an alarm notification.

Phone No.1

When Intellislot 1 Communication mode is Modem, this is the first phone

number to be dialed (to send an alarm notification).

Phone No.2

When Intellislot 1 Communication mode is Modem, this is the second phone

number to be dialed (to send an alarm notification).

Phone No.3

When Intellislot 1 Communication mode is Modem, this is the third phone

number to be dialed (to send an alarm notification).

Command password

User can modify the command password.

Command

(start/stop

battery &

system

tests)

Battery maintenance test

This test performs a partial discharge of the battery to obtain a rough estimate

of the battery capacity. Load must be between 20% and 80%.

Battery capacity test

This test performs a full discharge of the battery to obtain a precise measure of

the battery capacity. Load must be between 20% and 80%.

System test

This is a self-test of the UPS. When the user activates this function, a pop-up

window appears about 5 seconds later to show the results.

Stop testing

Manually stops a battery maintenance test, battery capacity test or system

test.

Freshening Charge

Allows a temporary Equalize charge for the batteries. This charge is

configurable for 1 to 36 hours.

Stop Freshening Charge

Manually stops a Freshening Charge

Modem Auto-answer

enable

Manually enable the modem’s auto-answer function.

Version

UPS version

Provides UPS firmware version numbers for the inverter, rectifier and software

display board.

UPS model

Provides UPS model information—for example, 208V-60Hz.

Table 22

Descriptions of UPS menus and data window items (continued)

Menu Type

Item Type

Explanation