R-5086

Figure 20

A =

*Clearance above grade, veranda, porch, deck or balcony [*12
inches (30cm) minimum]

B =

clearance to window or door that may be opened [*9 inches
(23cm) minimum for appliances < 50,000 Btuh (14.6kW)

C =

clearance to permanently closed window [minimum 12 inches
(30cm) recommended to prevent condensation on window]

D =

vertical clearance to ventilated soffit located above the terminal
within a horizontal distance of 24 inches (61cm) from the top of
the terminal

E =

clearance to unventilated soffitt [24 inches 61cm) minimum]

F =

clearance to outside corner [12 inches (30cm) minimum]

G =

clearance to inside corner [9 inches (22.5cm) minimum]

H =

*not to be installed above a meter/regulator assembly within 3
feet (90cm) horizontally from the center-line of the regulator

I =

clearance to service regulator vent outlet [*6 feet (1.8m)
minimum]

J =

clearance to non-mechanical air supply inlet to building or the
combustion air inlet to any other appliance [*12 inches (30cm)
minimum for appliances

100,000 Btuh (30 kW)

36 inches (90cm) minimum for appliances > 100,000 Btuh
(30kW)]

K =

clearance to a mechanical air supply inlet [* 6 feet (1.8m)
minimum]

L =

†clearance above paved sidewalk or a paved driveway located
on public property [*7 feet (2.1m) minimum]

M =

clearance under veranda, porch, deck, or balcony [*12 inches
(30cm) minimum¥]

a vent shall not terminate directly above a sidewalk or paved
driveway which is located between two single family dwellings
and serves both dwellings*

¥

only permitted if veranda, porch, deck, or balcony, is fully open
on a minimum of 2 sides beneath the floor*

*

as specified in CGA B149 Installations Codes or ANSI Z223.1.
Note: Local Codes or Regulations may require different
clearances.

Vent Clearances (Figure 20)