Specifications – Emerson 4-16kVA User Manual

Page 8

Advertising
background image

Emerson Network Power.
The global leader in enabling Business-Critical Continuity

.

EmersonNetworkPower.com

AC Power
Connectivity

DC Power

Embedded Computing

Embedded Power

Monitoring

Outside Plant

Power Switching & Controls

Racks & Integrated Cabinets

Services

Precision Cooling

Surge Protection

Liebert Corporation

1050 Dearborn Drive
P.O. Box 29186
Columbus, Ohio 43229
800 877 9222 Phone (U.S. &
Canada Only)
614 888 0246 Phone (Outside U.S.)
614 841 6022 FAX

Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD)

Italy
39 049 9719 111 Phone
39 049 5841 257 FAX

Emerson Network Power Asia Pacific
7/F., Dah Sing Financial Centre
108 Gloucester Rd, Wanchai
Hong Kong
852 25722201 Phone
852 28029250 FAX

liebert.com

24 x 7 Tech Support

800 222 5877 Phone
614 841 6755 (outside U.S.)

Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.
©2007 Emerson Electric Co.

While every precaution has been taken to ensure accuracy and
completeness in this literature, Liebert Corporation assumes no
responsibility, and disclaims all liability for damages resulting
from use of this information or for any errors or omissions.

© 2007 Liebert Corporation. All rights reserved throughout
the world. Specifications subject to change without notice.

All names referred to are trademarks or registered trademarks
of their respective owners.

® Liebert and the Liebert logo are registered trademarks
of the Liebert Corporation.

SL-23900 (R03/07) Printed in USA

Ensuring The High Availability Of
Mission-Critical Data And Applications

Scalable 12 - 20 kVA

Scalable 4 - 16 kVA

Specifications

General & Environmental

Units

Unit Rating

kVA

4

8

12

16

20

kW 2.8

5.6

8.4

11.2

14

Conducted and Radiated EMC Levels

FCC Part 15, Class A

Compliant Safety Standards

UL 1778; c-UL

Compliant Immunity Standards

IEEE C62.41, Category B

Mechanical

Units

8 Bay

12 Bay

Dimensions: Width

20 (508)

20 (508)

Dimensions: Depth

In (mm)

28 (711)

28 (711)

Dimensions: Height

41 (1041)

54 (1372)

Environmental

Units

4

8

12

16

20

Operating Temperature (max)

F (C)

32°-104° (0°-40°)

Relative Humidity

0-95% non-condensing

Maximum Operating Altitude

Ft. (M)

10,000 (3,000)

Nominal Heat Dissipation

BTU/Hr

1062

2124

3186

4248

5307

Input Data

Units

Nominal Input Voltage

VAC

170 to 276

VAC

110-276 (variable, based on output load)

Power Factor

Cos 0/

>.98

Input Frequency (nominal)

Hz

60

Input Frequency Range

Hz

40-70

Battery Module

Units

Battery Capacity

A/hr

9

Autonomy Time (full load)

Mins

7

(With an equal number of Battery & Power Modules, in a non-redundant configuration)

Maximum Charge Current (full load)

A

3

Nominal Voltage

VDC

120

Recharge Time

Hrs

3-5 (to 90% capacity)

Output Data

Units

Output Voltage

VAC

208/120 or 240/120

Voltage Regulation

%

±3

Voltage Transient Response (100% step load) %

±7

Voltage Stability (100% step load)

%

±7

Recovery Time

msec

96

Voltage distortion:

%

<3 THD, linear load

<7 THD, non-linear load

Output Frequency

Hz

60

Efficiency at 100% load

%

89

Output Overload Capability

%

110-125% for 10 min

126-150% for 10 sec

>151-200% for 2 cycles

Advertising
This manual is related to the following products: