Installation, Shields, Hart wiring connections – Emerson Process Management HF300 User Manual

Page 3: Hf300 series, Instruction manual

Advertising
background image

HF300 Series

Instruction Manual

Form 5715

June 2007

3

CONTROL

SYSTEM OUTPUT

TERMINALS

TYPE 2530H1 HART INTERCHANGE

MULTIPLEXER OR OTHER HART

MULTIPLEXER

FIELD

DEVICES

+

+

+

FLD TERMINALS

COMM TERMINALS

HF300 SERIES HART FILTER

+

+

SYS TERMINALS

HART MULTIPLEXER NETWORK

375 FIELD

COMMUNICATOR

+

Figure 2. Typical HF300 Series HART Filter Installation

Installation

Refer to figure 2 for typical installations. HF300

Series filters mount on a type 35 DIN rail. To install

the filter, provide a temporary means of process

control, then take the loop out of service. Remove

the DIN interconnect blocks from the rail without

disconnecting existing wiring. Install the filter on the

rail. Disconnect the wires from the control system

output side of the interconnect blocks and connect

them to the SYS terminals on the filter, taking care to

maintain correct polarity. Disconnect the wires from

the field side of the interconnect blocks and connect

them to the FLD terminals on the filter, taking care to

maintain correct polarity.

Shields

If using shielded wiring on both sides of the filter, the

shield should connect across the filter. If the filter

connects directly to the control system output and

shielded loop wiring is being used, connect the

shield to system ground on the instrument side of

the filter.

HART Wiring Connections

The COMM terminals on the filter provide a

convenient means to tap into the loop wiring for

HART communication. A HART Interchange

multiplexer or the 375 Field Communicator can be

connected to these terminals, or they may be left

with no connections.