System and Control Options

42

7.5.4 Change 4 mA Value

For the 4 mA value, enter the smallest value for the range of the sen-

sor—for example, 50°F for a temperature sensor with a range of 50°F

to 90°F.
The default value for each sensor is +045.0. Values that can be entered

range from -999.9 to +999.9.
To enter a new value:

• From the Setup Sensor Menu, choose 4 mA for the selected sensor

and press Enter

.

• To change the 4 mA value:

• Use the arrows

↑↓

to

choose a character.

• Press Enter

to advance to the next character position.

• When finished, press Enter

again.

7.5.5 Change 20 mA Value

For the 20 mA value, enter the largest value for the range of the sen-

sor—for example, 90°F for a temperature sensor with a range of 50°F

to 90°F.
The default value for each sensor is +096.0. Values that can be entered

range from -999.9 to +999.9.
To enter a new value:

• From the Setup Sensor Menu, choose 20 mA for the selected sen-

sor and press Enter

.

• To change the 20 mA value:

• Use the arrows

↑↓

to

choose a character.

• Press Enter

to advance to the next character position.

• When finished, press Enter

again.

7.5.6 Change Offset Value

For the Offset value, enter an adjustment factor—for example, if the

sensor reading shows 70°F when the actual temperature is 75°F, the

offset might be 5°F.
The default Offset value for each sensor is +000.0. Values that can be

entered range from -999.9 to +999.9.
To enter a new value:

• From the Setup Sensor Menu, choose Offset for the selected sensor

and press Enter

.

• To change the Offset value:

• Use the arrows

↑↓

to

choose a character.

• Press Enter

to advance to the next character position.

• When finished, press Enter

again.

Setup Sensor Menu

SETUP SENSOR_1

CONNECTED: Y
LABEL: ROOM_TMP

↑↓

=NEXT

=SELECT

UNITS: DEG

> 4 mA: +045.0

20 mA: +096.0
OFFSET: +000.0
ALARM/EVENT: AL
LATCHED: N
LOW SETPT: +0050.0
HIGH SETPT: +0090.0
SENSOR DELAY: 00:01

Change 4 mA Value

CHANGE 4 mA VALUE

4 mA: +050.0

↑↓

=SELECT

=NEXT/END

Setup Sensor Menu

SETUP SENSOR_1

CONNECTED: Y
LABEL: ROOM_TMP

↑↓

=NEXT

=SELECT

UNITS: DEG
4 mA: +050.0

> 20 mA: +096.0

OFFSET: +000.0
ALARM/EVENT: AL
LATCHED: N
LOW SETPT: +0050.0
HIGH SETPT: +0090.0
SENSOR DELAY: 00:01

Change 20 mA Value

CHANGE 20 mA VALUE

20 mA: +090.0

↑↓

=SELECT

=NEXT/END

Setup Sensor Menu

SETUP SENSOR_1

CONNECTED: Y
LABEL: ROOM_TMP

↑↓

=NEXT

=SELECT

UNITS: DEG
4 mA: +050.0
20 mA: +090.0

> OFFSET: +000.0

ALARM/EVENT: AL
LATCHED: N
LOW SETPT: +0050.0
HIGH SETPT: +0090.0
SENSOR DELAY: 00:01

Change Offset Value

CHANGE OFFSET VALUE

OFFSET: +005.0

↑↓

=SELECT

=NEXT/END