Ei Electronics Ei166R User Manual

Mains powered 230v~ rechargeable battery back-up, Model ei166r optical, Product description

Advertising
background image

Model

Ei166R Optical

Remote control capability

Easi-Fit base

Tamper proof rechargeable lithium battery back up

High performance optical chamber with integral
insect screen

Test/Hush button

Advanced suppression and calibration technology

Interconnectable to other Ei mains powered alarms

Built in auto self test feature

Low power cell warning

Kitemarked to BS5446-1:2000

5 year guarantee

Product Description

The Ei166R is an Optical Smoke Alarm that runs on
230V AC mains power, and has built in tamper proof
rechargeable lithium cells that act as a battery back up in
the event of mains failure. These rechargeable lithium
cells are designed to have a ten year life and outlast the
life of the smoke alarm itself, whilst providing up to six
months of smoke alarm operation without mains power.

The Ei166R is supplied with the Easi-Fit base that allows
very quick and simple installation of the smoke alarm,
combined with simple detector head removal and
replacement. The Easi-Fit base automatically connects
both mains power and battery as the detector head
slides on to the Easi-Fit base.

The Ei166R allows the detector to be controlled remotely
by either a “Test/Hush” Switch (Ei152), a “Locate” Switch
(Ei159) or a Manual Call Point (MCP400). If the Ei166R
is also interconnected to other Ei mains powered alarms
then the whole system can be controlled remotely.

The Ei166R has other advanced features such as
integral insect screens to reduce the chances of false
alarms, as well as the ability to interconnect up to twelve
alarms.

The Ei166R has built in circuitry to aid suppression of
voltage transients and RF interference to further reduce
the chances of false alarms under such conditions.

Operation

The green indicator will illuminate to show mains
power is present

The red indicator will flash every 40 seconds to
show that the detector has performed an automatic
self test

The red indicator will flash rapidly to show an alarm
condition for the smoke detector

The “Test/Hush” button will either silence false
alarms or perform a unit self test

In “Test” mode the alarm will perform a self test and
sound the horn

In “Hush” mode the alarm enters a ten minute period
of reduced sensitivity to overcome false alarm
conditions, and will then automatically reset itself

When interconnected to other Ei mains powered
alarms, an alarm on one detector will trigger all other
interconnected alarms within one second (only the
triggered alarm will flash a red indicator)

The smoke detector will emit a beep and flash the
red light every 40 seconds to indicate that the
battery back up is depleted and needs recharging

MAINS POWERED 230V~

Rechargeable Battery Back-Up

Shannon Free Zone, Shannon, Co. Clare, Ireland.

Ph.

+353 61 471277

Fx.

+353 61 471053

Email.

[email protected]

www.

eielectronics.com

Advertising