Air-Cooled Models—Self-Contained Compressor

29

Figure 15 General arrangement—Air-cooled models with fan speed control

DPN000349
Rev. 3

Condenser
Coil

Schrader
Valve

Fusible
Plug

Evaporator
Coil

Hot Gas
Bypass
Valve

Traps* every
25 ft. (7.6m)
of rise

Solenoid
Valves

Sight
Glass

Filter
Dryer

Liquid Return

Shutoff*
Valve

Sensing
Bulb

External Equalizers

Scroll
Compressor

Service
Valves

Hot Gas
Bypass

Hot Gas
Discharge

Check Valve

FIELD PIPING

FACTORY PIPING

*Components are not supplied by Liebert but
are recommended for proper circuit operation
and maintenance.

Expansion
Valve

Inverted Trap * on
discharge line to
extend above base
of coil by a minimum
of 7-1/2" (190mm)

Advertising