V4055A,B,D,E ON-OFF FLUID POWER GAS VALVE ACTUATOR

60-2309—1

3

2

ORDERING INFORMATION

When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the

TRADELINE® Catalog or price sheets for complete ordering number.

If you have additional questions, need further information, or would like to comment on our products or services, please write or

phone:

1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).

2. Honeywell Customer Care

1885 Douglas Drive North

Minneapolis, Minnesota 55422-4386

In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Toronto, Ontario M1V 4Z9.

International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,

Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.

SPECIFICATIONS

Models:

V4055A Actuator, with V5055, V5097 or VE5000 Gas Valves,

provides on-off control of fuel. With proper adapter (see

Accessories), it replaces the V4034 Actuator on a V5034

Gas Valve.

V4055B Actuator is a high pressure version of V4055A.

V4055D Actuator is identical to V4055A, except has a

Proof-of-Closure Switch. Used with V5055C/V5097C

(double seal) for valve seal overtravel interlock.

V4055E Actuator is identical to V4055B, except has a

Proof-of-Closure Switch. Used with V5055E/V5097E

(double seal) for valve seal overtravel interlock.

NEMA 4 weatherproof models available.

Nominal Opening Time: See Table 1.

Table 1. Nominal Opening Time (seconds).

Maximum Closing Time: One second when de-energized.

Ambient Operating Temperature Ratings:

60 Hz Models: -40°F to +150°F (-40°C to +66°C).

50 Hz, 50/60 Hz Models: -10°F to +158°F (-23°C to +70°C).

Mounting: V4055 Actuator attaches directly to V5055/V5097

Valve with two sets of screws positioned 90 degrees apart.

Combination is multipoise.

NOTE: 220 to 240 Vac, 50/60 Hz models are vertical

mount only.

Pressure Ratings: See Table 2.

Table 2. Pressure Ratings of Valve-Actuator Combinations.

a

Max Operating Pressure Differential (UL) or Max Operating Pressure (CSA): maximum allowable pressure drop from inlet to

outlet for proper operation .

b

Max rated pressure (UL) or Max Close-off Pressure (CSA) : maximum pressure that the valve can be exposed to without leak-

age or damage to the valve.

c

Applies for small-body V5097 valves 3/4” up to 2” pipe size.

d

Applies for large-body V5097 valves 2” up to 3” pipe size.

e

V5055A, B, C only.

Electrical Ratings: See Tables 3 and 4.

Model

50 Hz

60 Hz

Standard

32

26

Fast-opening

16

13

Model

Pipe Size

STANDARD PRESSURE ACTUATORS

V4O55A, D, F, G

HIGH PRESSURE ACTUATORS

V4O55B, E

M.O.P.D.

a

Max. Rated

Pressure

b

M.O.P.D.

a

Max. Rated

Pressure

b

STANDARD

PRESSURE VALVES

V5055A, B, C, F,

V5097A, B, C

3/4” to 1-1/2”

c

5 PSI

340 mbar 15 PSI

1.0 Bar

15 PSI

1030 mbar 15 PSI

1.0 Bar

2” to 3”

d

5 PSI

340 mbar 15 PSI

1.0 Bar

15 PSI

1030 mbar 15 PSI

1.0 Bar

4” flanged

e

3 PSI

207 mbar 15 PSI

1.0 Bar

5 PSI

340 mbar

15 PSI

1.0 Bar

HIGH PRESSURE

VALVES V5055D, E,

V5097D, E

3/4” to 1-1/2”

c

5 PSI

340 mbar 75 PSI

5.0 Bar

25 PSI

1720 mbar 75 PSI

5.0 Bar

2” to 3”

d

5 PSI

340 mbar 45 PSI

3.0 Bar

15 PSI

1030 mbar 45 PSI

3.0 Bar