J3 wiring chart – Hubbell Electric Heater Company J User Manual

Page 17

Advertising
background image

J3 Wiring Chart

kW

Volt

Ph

Unit

Amp

Draw

Phase-

Phase

Resistance

(Ohms)

Min.
Feed

Breaker

or Fuse

Size

Internal

Power

Wire

Size

Element

Jumper

Wire

Size

Copper

Power Feed

Wire Size

Conduit

Size

Diagram

2.9

120

1

23.8

5.0

30

12

12

10

½"

4

5.7

120

1

47.5

2.5

60

10

12

6

¾"

4

208

1

47.6

4.4

60

10

12

6

¾"

4

208

3

27.5

8.7

35

12

12

8

½"

10 (NT)

208

1

51.9

4.2

65

10

12

6

¾"

4

208

3

28.8

8.3

40

12

12

8

½"

10 (NT)

240

1

47.5

5.1

60

10

12

6

¾"

4

240

3

27.4

10.1

35

12

12

8

½"

10 (NT)

277

1

41.2

6.7

55

10

12

6

¾"

4 (WT)

380

3

16.8

25.3

25

12

12

12

½"

14

415

3

15.9

30.2

20

12

12

12

½"

14

480

3

13.7

40.4

20

12

12

14

½"

14

600

3

11.0

63.2

15

12

12

14

½"

14

9.9

10.4

11.4


J3 Wiring Chart Notes:
1. Power feed wire sizing is based on using 75°C Cu THHN wire with feeder branch

protection rated at 125%.

2. Internal wire sizing is based on using 200°C SEW-2 or PTFE wiring in a raceway

with an ambient temperature up to 60°C.

3. Normal phase-to-phase resistance tolerance is ±5%.
4. 277, 380,415, 480, and 600-volt phase-to-phase resistance values are shown with the

transformer disconnected.

J4 Wiring Chart

kW

Volt

Ph

Unit

Amp

Draw

Phase-

Phase

Resistance

(Ohms)

Min.
Feed

Breaker

or Fuse

Size

Internal

Power

Wire

Size

Element

Jumper

Wire

Size

Copper

Power Feed

Wire Size

Conduit

Size

Diagram

208

1

54.1

3.8

70

8

8

4

1"

4

208

3

31.2

7.7

40

8

8

8

½"

10 (NT)

220

1

57.3

3.8

75

8

8

4

1"

4

220

3

33.1

7.7

45

8

8

8

½"

10 (NT)

230

1

59.8

3.8

75

8

8

4

1"

4

230

3

34.5

7.7

45

8

8

8

½"

10 (NT)

240

1

62.5

3.8

80

8

8

4

1"

4

240

3

36.1

7.7

50

8

8

8

½"

10 (NT)

480

3

18.0

30.7

25

12

12

10

½"

10 (WT)

208

3

75.0

3.2

95

6

8

3

1"

10 (NT)

240

3

65.0

4.3

85

8

10

4

1"

10 (NT)

480

3

32.5

17.1

45

12

12

8

½"

10 (WT)

13.8

11.3

12.6

15

27


J4 Wiring Chart Notes:
1. Power feed wire sizing is based on using 75°C Cu THHN wire with feeder branch

protection rated at 125%.

2. Internal wire sizing is based on using 200°C SEW-2 or PTFE wiring in a raceway

with an ambient temperature up to 60°C.

3. Normal phase-to-phase resistance tolerance is ±5%.
4. 480-volt phase-to-phase resistance values are shown with the transformer disconnected.

Advertising