Burner operation, Lighting instructions – HP SU-2A User Manual

Page 11

Advertising
background image

11

LIGHTING INSTRUCTIONS

To light the SU-2A Gas Burner

1. Set the thermostat to the lowest

temperature

2. The control knob on the gas

valve should be in the “OFF”

position for at least five minutes.

3. Rotate the control knob counter-

clockwise to the “ON” position

and set the thermostat to the

desired temperature settings

Reset, if Flame Lockout Occurs

1. Turn the thermostat off, or turn the main power off

2. Wait five minutes

3. Turn the main power on

To shut the burner off

1. Rotate the control knob on the gas valve to the

“OFF” position

2. Set the thermostat to the lowest temperature

3. Turn Main Power Off.

BURNER OPERATION

Before turning the burner on, check for gas supply leaks. Check the wiring diagrams; install

manometers before and after the gas valve. Keep the observation port of the boiler or furnace

open. Follow the instructions on the nameplate of the burner to turn it on. Follow the sequence

of operations for the control (see pages 9 and 10).

Use a combustion analyzer and record the

readings below.

BURNER OPERATION: Record the Readings at Steady State

Draft over fire at steady state (should be –0.02 “W.C. or zero)

NOTE: This may vary for OEM applications.

Natural Gas CO

2

% = (9.0% to 9.8%) or O

2

% = (5.0% to 3.5%)

LP Gas CO

2

% = (10.5% to 11.5%) or O

2

% = (5.0% to 3.5%)

Stack Temperature (300

o

F minimum, 550

o

F maximum)

Percentage of Carbon Monoxide (CO) in PPM

Incoming Gas/LP pressure = “W.C. (minimum 5”)

Natural Gas manifold gas pressure = “W.C. (3.5” required + - 0.3”)

NOTE: This may vary for OEM applications.

LP Gas manifold gas pressure = “W.C. (2.3” required + - 0.3”)

Carbon Monoxide in flue ( less than 100 PPM ideal; should not exceed

400 PPM Oxygen free)