Diagnostics, Beacon ii troubleshooting guide (continued) – Heatcraft Refrigeration Products BEACON II H-IM-79E User Manual

Page 24

Advertising
background image

24

Beacon II Troubleshooting Guide (continued)

Diagnostics

PROBLEM

Step ACTION ITEM

IF OK

IF NOT OK

1.

Check wiring connection to the board

• Correct field wiring to the board

2.

Low Pressure Safety (LPS) Tripped:

• Check for correct refrigerant type

• Change setpoint to match refrigerant

• Check refrigerant charge

• Add more refrigerant to proper charge

• Check LPS setting

• Correct LPS setting

• Check LPS wiring

• Correct LSP wiring

• Check EEV operation (stuck?)

• Clean or replace EEV

• Check coil for icing

• Defrost coil (see E6, step 2)

• Check for correct superheat reading

• Check/replace sensor or transducer

• Check for correct nozzle selection

• Replace distributor nozzle

• Check for clogged EEV inlet screen

• Replace EEV

• Check line sizing

• Correct line sizing

• Check LPS time delay relay setting

• Reset to 1 minute

• Check operation of LPS

• Replace Low Pressure Safety Switch

3.

High Pressure Safety (HPS) Tripped:

• Check for system overcharge

• Reclaim/recover excess charge

• Check for non-condensables

• Remove all non-condensables

• Check condenser fan motor and blade

• Repair or replace motor and/or blade

• Check for dirty condenser coil

• Clean condenser coil

• Check head pressure controls

• Adjust or replace faulty controls

• Check fan cycling controls

• Adjust or replace faulty controls

• Check liquid line sizing

• Correct line sizing

• Check for liquid line restrictions

• Repair line or remove restrictions

• Check operation of HPS

• Replace HPS if necessary

E7 Compressor

4.

Oil Pressure Safety (OPS) Tripped:

Shutdown

• Check oil level in compressor

• Add oil to crankcase to minimum level

• Check oil sump screen pickup

• Clean or replace pickup screen

• Check oil pump pressure

• Replace compressor oil pump

• Check for proper piping practices

Go to

• Correct piping to minimize oil logging

• Check for low superheat (see E6)

next step • Correct per steps in E6

• Check operation of auxiliary relay (R6)

• Replace auxiliary relay

• Check OPS sensor

• Replace faulty OPS sensor

• Check operation of OPS

• Replace faulty OPS

5.

Compressor Module Tripped (when supplied):

• Check module

• Replace faulty module

• Check superheat at compressor inlet

• Reduce superheat (TXV adjust, etc.)

• Check compressor for overheating

• Correct overheating problem

• Check suction pressure (too low?)

• Consider crankcase pressure regulator

or other measures

6.

Phase Loss Monitor (PLM) Tripped:

• Check presence of all phase legs

• Correct power phase problem

• Check power supply

• Correct power supply problems

• Check operation of PLM

• Replace faulty PLM

7.

Demand Cooling (when supplied):

• Check auxiliary relay

• Replace auxiliary relay

• Check demand cooling device

• Replace faulty demand cooling device

8.

Check compressor relay on board

• Replace board if relay is faulty