BEACON CONTROLLER

12

Error Codes

One blink — Superheat sensor shorted or open

Two blinks — Room temperature sensor shorted or jumper not installed

Three blinks — Compressor discharge temperature sensor shorted

Four blinks — High compressor discharge temperature

Five blinks — Superheat too low

Six blinks — High pressure, oil pressure or low pressure cut-out

Seven blinks — Defrost Termination sensor shorted.

Note: See Table 2 for thermistor sensor resistance values at selected temperatures. To check a sensor,
place it in an ice bath (a cup with ice and water) and stir. The resistance should be 32,650 ohms at the 32

°

F

bath temperature.

EVAPORATOR FANS SHUT-DOWN BY OPERATORS

In some installations, a switch is provided which allows an operator to de-energize the evaporator fans while
loading the freezer or cooler box. This may cause the evaporator coil to freeze-up. The compressor can be
de-energized when the evaporator fan is de-energized, by wiring a 24V AC coil, double pole single throw
(DPST), relay into the fan circuit. This relay, R3, and the wiring is shown on the TYPICAL WIRING SCHE-
MATICS
, in the back of this installation manual. For multiple evaporators, additional relays wired in parallel to
R3, to break the other fans, will be needed.

STATUS INDICATOR LIGHT BLINK SEQUENCE

Mode

Blink Time

Off Time

Action

Cooling

2 sec.

2 sec.

Faster blinks for superheat count, then repeat

Off

1 sec.

7 sec.

Repeat

Defrost

1 sec.

1 sec.

Repeat

Error

8 fast

2 sec.

Slower blinks for error code, then repeat

Resistance of thermistor sensors at various temperatures.

Temperature

°

F

Ohms

Temperature

°

F

Ohms

104

5,320

32

32,650

86

8,060

23

42,330

77

10,000

14

55,330

68

12,490

5

72,950

59

15,710

-4

97,070

50

19,900

-13

130,410

41

25,400

-22

176,960

TABLE 2