60 Hz Performance
Model
Capacity
BtUH/
watts
10°F tD
-0°F SSt
Fan Data
Standard Motor Data
Defrost Heaters
HP
total amps
Watts
total amps
CFM/
m
3
h
no. Dia.
in./
mm
air throw ft./
m
08-30/1/60 08-
30
/3/60
460/1/60
460
/3/60
575
/3/60
08-
30
/3/60
460
3/60
575
/3/60
Standard
w/
Collar
Wired
1-Phase
Wired
3-Phase
Wired
1-Phase
Wired
3-Phase
BHe Models 6 Fins Per inch
BHE450 45,000
13,00
9,000
15,300
2 24
610
70
1
85
6
1/2*
6.4
-
5.2
3.4
-
2.6 1.8 9,900 27.5 13.9 11.1
BHE550 55,000
16,100
9,000
15,300
2 24
610
70
1
85
6
1/2*
6.4
-
5.2
3.4
-
2.6 1.8 9,900 27.5 13.9 11.1
BHE640 64,000
18,700
12,600
1,400
3 24
610
70
1
85
6
1/2*
-
5.5
7.8
-
3.0
3.9 2.7 12,900 35.8 18.1 14.5
BHE740 74,000
1,700
12,600
1,400
3 24
610
70
1
85
6
1/2*
-
5.5
7.8
-
3.0
3.9 2.7 12,900 35.8 18.1 14.5
BHE810 81,000
3,700
16,800
8,600
4 24
610
70
1
85
6
1/2*
-
8.7
10.4
-
4.7
5.2 3.6 17,050 47.8 24.3 19.1
BHE950 95,000
7,800
16,800
8,600
4 24
610
70
1
85
6
1/2*
-
8.7
10.4
-
4.7
5.2 3.6 17,050 47.8 24.3 19.1
BHE1020 102,000
9,900
20,700
35,00
3 30
76
100
30
115
35
1
-
-
13.8
-
-
6.9 7.8 21,400 64.2 32.1 22.8
BHE1200 120,000
35,100
20,700
35,00
3 30
76
100
30
115
35
1
-
-
13.8
-
-
6.9 7.8 21,400 64.2 32.1 22.8
BHE1390 139,000
40,700
24,300
41,300
3 30
76
100
30
115
35
1-1/2
-
-
19.8
-
-
9.9 7.8 21,400 64.2 32.1 22.8
BHE1650 165,000
48,300
26,550
45,100
3 30
76
120
37
140
43
1-1/2
-
-
21.0
-
-
10.5 8.4 33,600 87.2 47.5 34.9
BHE2120 212,000
6,100
35,400
60,00
4 30
76
120
37
140
43
1-1/2
-
-
28.0
-
-
14.0 11.2 49,600 128.4 70.0 56.0
BHL Models 4 Fins Per inch
BHL400 40,000
11,700
9,400
16,000
2 24
610
70
1
85
6
1/2*
6.4
-
5.2
3.4
-
2.6 1.8 9,900 27.5 13.9 11.1
BHL480 48,000
14,100
9,400
16,000
2 24
610
70
1
85
6
1/2*
6.4
-
5.2
3.4
-
2.6 1.8 9,900 27.5 13.9 11.1
BHL560 56,000
16,400
13,200
,400
3 24
610
70
1
85
6
1/2*
-
5.5
7.8
-
3.0
3.9 2.7 12,900 35.8 18.1 14.5
BHL650 65,000
19,000
13,200
,400
3 24
610
70
1
85
6
1/2*
-
5.5
7.8
-
3.0
3.9 2.7 12,900 35.8 18.1 14.5
BHL710 71,000
0,800
17,600
9,900
4 24
610
70
1
85
6
1/2*
-
8.7
10.4
-
4.7
5.2 3.6 17,050 47.8 24.3 19.1
BHL840 84,000
4,600
17,600
9,900
4 24
610
70
1
85
6
1/2*
-
8.7
10.4
-
4.7
5.2 3.6 17,050 47.8 24.3 19.1
BHL890 89,000
6,100
21,600
36,700
3 30
76
100
30
115
35
1
-
-
13.8
-
-
6.9 7.8 21,400 64.2 32.1 22.8
BHL1050 105,000
30,800
21,600
36,700
3 30
76
100
30
115
35
1
-
-
13.8
-
-
6.9 7.8 21,400 64.2 32.1 22.8
BHL1220 122,000
35,700
25,200
4,800
3 30
76
100
30
115
35
1-1/2
-
-
19.8
-
-
9.9 7.8 21,400 64.2 32.1 22.8
BHL1440 144,000
4,00
27,600
46,900
3 30
76
120
37
140
43
1-1/2
-
-
21.0
-
-
10.5 8.4 33,600 87.2 47.5 34.9
BHL1860 186,000
54,500
36,800
6,600
4 30
76
120
37
140
43
1-1/2
-
-
28.0
-
-
14.0 11.2 49,600 128.4 70.0 56.0
table . Models BHe/BHL 60 Hz electric Defrost
* 208-230/3/60 and 460/3/60 motors are 3/4 HP
Notes: TD = Temperature Difference = (Room temperature - saturated suction temperature)
Saturated Suction Temperature °F
+20
-10
-20
-30
-40
Saturated Suction Temperature °C
-7
-23
-29
-34
-40
Multiply Capacity By
1.15
1.04
1.00
0.90
0.80
Capacity Correction Factors for electric and Hot gas Defrost Units