Connections, Default setting values, Dixel – Hill Phoenix P074749F User Manual

Page 28: Dixel operating manual, S.p.a

Advertising
background image

dIXEL

Operating Manual

1592020130

1592020130 XR03_04CX GB 16.01.07.doc

XR03CX – XR04CX

Protection: IP20; Frontal protection: IP65
Connections: Screw terminal block

≤ 2,5 mm

2

wiring.

Power supply: according to the model: 12Vac/dc, ±10%; 24Vac/dc, ±10%; 230Vac

±10%, 50/60Hz,

110Vac

±10%, 50/60Hz

Power absorption: 3VA max

Display: 2 digits, red LED, 14,2 mm high; Inputs: Up to 2 NTC or PTC probes.

Digital input: free voltage contact

Relay outputs: compressor SPST 8(3) A, 250Vac; or 20(8)A 250Vac

defrost or Aux: SPDT 8(3) A, 250Vac

Data storing: on the non-volatile memory (EEPROM).

Kind of action: 1B; Pollution grade: 2;Software class: A.;
Rated impulsive voltage: 2500V; Overvoltage Category: II

Operating temperature: 0÷60 °C; Storage temperature: -30÷85 °C.
Relative humidity: 20

÷85% (no condensing)

Measuring and regulation range: NTC probe: -40÷110°C (-40÷230°F);

Resolution: 0,1 °C or 1°C or 1 °F (selectable); Accuracy (ambient temp. 25°C): ±0,7 °C ±1 digit

14. CONNECTIONS

XR03CX –20A o 8A Compressor

NOTE: The compressor relay is 20(8)A or 16(6)A depending on the model.

NOTE: 120Vac or 24Vac/dc or 12Vac/dc connect to 6-7
XR04CX –20A o 8A Compressor

NOTE: The compressor relay is 20(8)A or 16(6)A depending on the model.

NOTA: 120Vac o 24Vac/dc o 12Vac/dc connect to 6 and 7

15. DEFAULT SETTING VALUES

LAB

EL

DESCRIPTION

RANGE

DEFAULT

REGULATION

Hy

Differential

0.1 ÷ 25°C/1 ÷ 45°F

2.0°C / 4 °F

LS

Minimum Set Point

-55°C÷SET/-67°F÷SET

-55 °C /-

55°F

US

Maximum Set Point

SET÷99°C/ SET÷210°F

99 °C /

99°F

ot

First probe calibration

-9.9÷9.9°C/-18÷18°F

0.0

P2

Second probe presence (Only
XR04CX)

n – Y

y

oE

Second probe calibration (Only
XR04CX)

-9.9÷9.9°C/-18÷18°F 0.0

od

Outputs activation delay at start up

0 ÷ 99 min

0

AC

Anti-short cycle delay

0 ÷ 50 min

1

Cy

Compressor ON time faulty probe

0 ÷ 99 min

15

Cn

Compressor OFF time faulty probe

0 ÷ 99 min

30

CH

Kind of Action (Only XR03CX)

cL ÷ Ht

cL

DISPLAY

CF

Measurement units

°C - °F

°C / °F

rE

Resolution (only for °C)

dE – in

dE

Ld

Default Display (Only XR04CX)

P1-P2 - SP

P1

dy

Display delay

0 ÷ 15 min

0

DEFROST

td

Defrost type

EL – in

EL

dE

Defrost termination temperature

-50÷50°C/-58÷122°F

8.0 °C / 46

°F

id

Interval between defrost cycles

0 ÷ 99 hours

6

Md

Maximum length for defrost

0 ÷ 99 min.

30

dd

Start defrost delay

0 ÷ 99 min.

0

dF

Display during defrost

rt – in – SP – dF

it

dt

Drip time

0 ÷ 99 min

0

dP

Defrost at power-on

y - n

n

ALARMS

AU

Maximum temperature alarm

ALL÷99°C / ALL÷210°F

99 °C / 99

°F

AL

Minimum temperature alarm

-55°C÷ALU/-67°F÷ALU

-55 °C / -55

°F

Ad

Temperature alarm delay

0 ÷ 99 min

15

dA

Exclusion of temperature alarm at
startup

0 ÷ 99 min

90

DIGITAL INPUT (Only XR03CX)

iP

Digital input polarity

cL – oP

cL

iF

Digital input configuration

EA – bA – do – dF –

Au– db

EA

di

Digital input delay

0 ÷ 99 min

5

dC

Compressor and fan status when open
door

no /Fn / cP / Fc

FC

rd

Regulation with door open

n - Y

y

OTHER

d1

Thermostat probe display

Read Only

- - -

d2

Evaporator probe display

Read Only

- - -

Pt

Parameter code table

Read Only

- - -

rL

Firmware release

Read Only

- - -

dIXEL

S.p.a.

Z.I. Via dell’Industria, 27 - 32010 Pieve d’Alpago (BL) ITALY
tel. +39 - 0437 - 98 33 - fax +39 - 0437 - 98 93 13

http://www.dixell.com