Quick Start Guide for Herculine 2000 Series

Group
Prompt

Function
Prompt

Value or
Selection

Factory
Setting

RELAYn

RTYP

NONE

RnyE

X1

RnyVAL

0.0

RnyHL

LO

RLYnHY

0.0

CU OUT

CUROUT

NONE
Depends on
MSG

COMM

COMM

DIS

ADDRES

1

BAUD

19.2

XmtDLY

20ms

DBLBYT

FP

B

DIGINP

DIGINP

NONE

EndPos

0

DISPLA

DECMAL

8888

EUNITS

PCNT

UNITS

ENGL

LOCK

LOCKID

0

LOCK

NONE

MAENAB

ENAB

STATUS

FAILSF

Read Only

Read Only

RAMTST

Read Only

Read Only

SEETST

Read Only

Read Only

CFGTST

Read Only

Read Only

CALTST

Read Only

Read Only

DRVINF

VERSON

Read Only

Read Only

SPEED

Read Only

Read Only

POWER

Read Only

Read Only

ROTATE

Read Only

Read Only

TAG

6

alpha

characters

MFGDAT

Read Only

Read Only

LREP

Factory Set

Factory Set

LCAL

Factory Set

Factory Set

REPTYP

Factory Set

Factory Set

Group
Prompt

Function
Prompt

Value or
Selection

Factory
Setting

MAINT

TEMP

NONE

TEMPHI

X1

TEMPLO

0.0

hh:mm:ss

ACST

Read

Only

STARTS

Read

Only

Accumulated
Motor Starts

RnCNT

n=1,2,3,or4

Read Only

Relay Cycle
Counts

REGNn

n= 0 to 9

Read Only

Accumulated
Motor Starts

TOTDEG

Read Only

Total Degrees of
Motor Travel

DATSAV

DIS

PASSWRD

Nnnn

MANRST

NONE

LD

CAL

NONE

LD

CFG

DIS

RESTRT

DIS

7. Start up/Operation

After the actuator is completely installed, wired, and
the preliminary adjustments made, check the
operation of the actuator and controlled device
before placing it in service. Operate the controlled
device and check its direction of travel in response
to an increase of the input signal and make sure it is
correct for the process. Actuators having the
optional auto-manual switch must have the knob set
in the AUTO position.
When power is applied to the actuator, the actuator
electronics performs a diagnostic routine on various
device components. These tests include a:

RAM diagnostic (RAMTST),

Check of the electrically eraseable PROM
(SEETST),

Verification that valid parameter values are
in the actuator configuration (CFGTST),

Verification of valid calibration values
(CALTST)

Test of the local display and LED indicators
(all display segments and LED indicators
light simultaneously).

The optional local display shows the status of the
diagnostics as they are completed during power up.
TEST DONE is shown on the display when
diagnostics are complete and actuator should be in
AUTO mode.

If the Actuator Motor is “Hunting” (Motor does not
drive to a position and stop) the process control
loop is not tuned correctly. Refer to the Instruction
Manual for your controller on how to tune a loop.

Advertising