SOLID CORE AND SPLIT CORE 4-20 MA OUTPUT CURRENT SENSORS

Automation and Control Solutions
Honeywell International Inc.

Honeywell Limited-Honeywell Limitée

1985 Douglas Drive North

35 Dynamic Drive

Golden Valley, MN 55422

Toronto, Ontario M1V 4Z9

customer.honeywell.com

® U.S. Registered Trademark
© 2007 Honeywell International Inc.
62-0245—01 C.H. Rev. 06-07

TROUBLESHOOTING

CURRENT CONVERSION FORMULA

To convert the current sensor output signal to a current
reading.

Current reading = mA output/20 mA x Amp Span.
For example:
For a reading of 4 mA with a 0-250 Amp span:
Current reading = (4 mA/20 mA) x 250 A = 0 Amp.
(0/16) X 250 = 0

NOTE: 4 mA = 0 Amps

20 mA = 250 Amps

Problem

Solution

No reading

• Confirm that you have +12 to 30 Vdc in series with the current sensor output terminals

and the analog input of the control panel.

• Check the polarity of the circuit.
• Verify that the terminals are screwed down, wires are firmly in place.
• Disconnect the input to the control panel and then insert a current meter (mA range) in

series with the current sensor output to verify that the circuit is working properly.

Erratic readings

• Verify that the wires are terminated properly.
• Check that the +12 to 30 Vdc input is clean. In areas of high RF interference, shielded

cable may be necessary to stabilize signal.

Inaccurate readings

• If you suspect that the current sensor is not reading within the accuracy specifications,

please contact the factory for assistance.