Heatilator • GDST3831I • 2127-900 Rev. L • 3/13

24

A. Approved Pipe

This appliance is approved for use with Hearth & Home
Technologies a SLP venting system. Refer to Section
16B for vent component information.

DO NOT mix pipe, fi ttings or joining methods from differ-
ent manufacturers.

The pipe is tested to be run inside an enclosed wall.
There is no requirement for inspection openings at each
joint within the wall.

WARNING! Risk of Fire or Asphyxiation. This appli-
ance requires a separate vent. DO NOT vent to a pipe
serving a separate solid fuel burning appliance.

C. Use of Elbows

Diagonal runs have both vertical and horizontal vent as-
pects when calculating the effects. Use the rise for the
vertical aspect and the run for the horizontal aspect (see
Figure 7.1).

Two 45º elbows may be used in place of one 90º elbow.
On 45º runs, one foot of diagonal is equal to 8-1/2 in. (216
mm) horizontal run and 8-1/2 in. (216 mm) vertical run. A
length of straight pipe is allowed between two 45º elbows
(see Figure 7.1).

Figure 7.1

7

7

Vent Information and Diagrams

B. Vent Table Key

The abbreviations listed in this vent table key are used in
the vent diagrams.

D. Measuring Standards

Vertical and horizontal measurements listed in the vent
diagrams were made using the following standards.

• Pipe measurements are shown using the effective length

of pipe (see Figure 7.2).

• Horizontal terminations are measured to the outside

mounting surface (fl ange of termination cap) (see Figure
6.1).

• Vertical terminations are measured to bottom of

termination cap.

• Horizontal pipe installed level with no rise.

Symbol

Description

V

1

First section (closest to appliance) of vertical length

V

2

Second section of vertical length

H

1

First section (closest to appliance) of horizontal length

H

2

Subsequent sections of horizontal length

Horizontal

Vertical

8-1/2 in.

8-

1

/2

i

n

.

12

in

.

Figure 7.2 SLP Pipe Effective Length

Effective Height/Length

Pipe

inches

mm

SLP4

4

102

SLP6

6

152

SLP12

12

305

SLP24

24

610

SLP36

36

914

SLP48

48

1219

SLP6A

2 - 6

51 - 152

SLP12A

2 - 12

51 - 305

SLP-FLEX-2

24

610

SLP-FLEX-3

36

914

SLP-FLEX-5

60

1524

SLP-FLEX-10

120

3048

Effective

Height/

Length