RECOMMENDED PERIODIC TESTING

TESTING
ITEM

HOW

OFTEN

COMPLETED

BY


REMARKS

Gauges, monitors and operating log

Daily

Operator

Make visual inspection and record readings

Instrument and equipment settings

Daily

Operator

Make visual check against recommended
specifications

Weekly

Operator

Verify factory settings

Semiannually

Service Tech

Verify factory settings

Firing rate

Annually

Service Tech

Check with combustion test

Flue, vent, stack or outlet dampers

Monthly

Operator

Make visual inspection of linkage; check for
proper operation

Igniter

Weekly

Operator

Make visual inspection, check flame signal
strength if meter-fitted (see "Combustion Safety
Controls")

Fuel valves: pilot and main
(primary and secondary)

Weekly

Operator

Operate burner. Using a manometer or pressure
gauge, check pressure to the burner as required
on rating label.

Pilot and main gas or oil train

Annually

Service Tech

Perform leakage tests - refer to instructions

Combustion safety controls (flame
failure)

Weekly

Operator

Close manual fuel supply for the pilot and main
fuel valve(s); check safety shutdown timing; log
result.

Flame signal strength



Weekly

Operator

With flame signal meter installed, read and log
for both pilot and main flames. Notify service
organization if readings are very high, very low
or fluctuating. Refer to instructions for nominal
values

Pilot turndown test

As required /

annually

Service Tech

Required after any adjustment to flame scanner
mount or pilot burner; verify annually - refer to
instructions.

Low-water fuel cutoff and alarm

Daily/weekly

Semiannually

Operator

Refer to instructions and perform a slow drain
test.

High limit safety thermostat control

Annually

Service Tech

Refer to instructions

Operating thermostat control

Annually

Service Tech

Refer to instructions

Vent draft fan, and air pressure
switches

Monthly

Operator

Refer to instructions

High and low gas pressure interlocks

Monthly

Operator

Refer to instructions

High and low oil pressure interlocks

Monthly

Operator

Refer to instructions

Fuel valve interlock switch

Annually

Operator

Refer to instructions

Low fire start interlock

Annually

Operator

Refer to instructions

Automatic changeover control (dual
fuel)

At least

annually

Service Tech

Under supervision of gas utility

T&P valves


As required

Operator

In accordance with procedure in Section VI
ASME Boiler and Pressure Vessel Code,
Recommended Rules for Care and Operation of
Heating Boilers.