For Vertical Runs - One ceiling firestop is REQUIRED at

the hole in each ceiling through which the vent passes.
To install firestops for vertical runs that pass through ceilings:
• Position a plumb bob directly over the center of the verti-

cal vent component.

• Mark the ceiling to establish the centerpoint of the vent.
• Drill a hole or drive a nail through this centerpoint.
• Check the floor above for any obstructions, such as wir-

ing or plumbing runs.

• Reposition the fireplace and vent system, if necessary,

to accommodate the ceiling joists and/or obstructions.

• Cut an 11-inch X 11-inch (280mm X 280mm) hole through

the ceiling, using the centerpoint previously marked.

• Frame the hole with framing lumber the same size as the

ceiling joists.

Figure 18. Ceiling Firestop (Ceiling Side)

If the area above the ceiling is NOT an attic, position and

secure the ceiling firestop on the ceiling side of the previously

cut and framed hole.

Figure 17. 11" x 11" Hole & New Framing Members

If the area above the ceiling IS an attic, position and secure

the firestop on top of the previously framed hole.
NOTE: Keep insulation away from the vent pipe at least

1 inch (25mm).

Figure 19. Attic Firestop

JOIST

CEILING FIRESTOP

CEILING

NAILS (4 REQUIRED)

CEILING

CEILING FIRESTOP

RAFTER

NAILS (4 REQUIRED)

CEILING

NEW
FRAMING
MEMBERS

EXISTING CEILING
JOISTS

CHIMNEY
HOLE

11" (280 mm)

11" (280mm)