Alarms, W7751 controller status led, W7751h – Honeywell EXCEL 10 W7751H User Manual

Page 10

Advertising
background image

EXCEL 10 W7751H SMART VAV ACTUATOR

95-7553—04

10

NOTE: During item 2, the occupancy override state of

the controller changes based on how long the

bypass/override button is depressed. For

example, if the button is pressed for 6 sec., the

node sends the Service Pin Message, AND the

node enters Continuous Unocc mode. To clear

Continuous Unocc mode, the button must be

pressed momentarily.

3. The following method is only supported on E-Vision and

L

ON

S

PEC

™:

a. When an Assign ID command is issued from the

Honeywell Software listed, the node enters the

SERVICE_MESSAGE mode for five minutes.

b. In this mode, pressing the bypass/override button

causes the Service Message to be broadcast on the

network.

c. All other functions are normal in this mode.

d. If the bypass/override button is not available, short-

ing the controller Bypass Input terminals (on

W7751H short terminals 5 and 7) broadcasts the

Service Message.

Alarms

The commissioning tool is used to perform the ID Assignment

task. Once the ID Assignment and commissioning has been

done, check the controller status LED to determine if there are

any alarms.

W7751 Controller Status LED

The LED on the front of a W7751H Controller (located just

under the plastic cover), provides a visual indication of the

status of the device. When the W7751H receives power, the

LED appears in one of the following allowable states:

1. Off—no power to the processor.

2. Continuous on—processor is in initialized state.

3. Slow blink—controlling, normal state.

4. Fast blink—when the Excel 10 VAV Controller has an

alarm condition.

When an Excel 10 has an alarm condition, it reports it to the

central node on the L

ON

W

ORKS

® Bus. Also, the Excel 10 VAV

Controller variables, AlarmLogX, where X is 1 through 5, that

store the last five alarms to occur in the controller, are

available. These points can be viewed through workstation

software. Refer to the VAV System Engineering Guide form,

74-2949 Table 12 for a description of the Excel 10 Alarms.

NOTE: The node can be reset by switching the node to

MANUAL and then to the normal operating mode.

Fig. 19. W7751H to PWM Valve Actuator.

1

2

3

4

5

6

7

8

9

10

11

12

24 VAC

COM

OUT 1

OUT 2

E-BUS

24 VAC

W7751H

M10528

WALL MODULE

EARTH

GND

SENSOR

BYPASS

LED

NOT EARTH GROUND

TRIAC
EQUIVALENT
CIRCUIT

2

2

1

1

2

MAKE SURE ALL TRANSFORMER/POWER WIRING IS AS SHOWN;
REVERSING TERMINATIONS WILL RESULT IN EQUIPMENT MALFUNCTION.

TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST
BE TWISTED TOGETHER BEFORE INSERTING INTO THE TERMINAL BLOCK.

ML7984B

PERIPHERAL REHEAT

VALVE ACTUATOR

PWM OUTPUT FROM CNTRL

PWM (H 24 VAC)

PWM VALVE ACTUATOR

24 (N)

24

(H)

T6

T5

C

B

W

R

ML7984B

REHEAT VALVE

ACTUATOR

PWM OUTPUT FROM CNTRL

PWM (H 24 VAC)

PWM VALVE ACTUATOR

24 (N)

24

(H)

T6

T5

C

B

W

R

ON

OFF

1

2

3

4

CONFIGURATION DIP SWITCHES

LOCATED ADJACENT TO THE INPUT

TERMINAL BLOCK ON ML7948B

SET PT