Locking beacon ii board, Status indicator led -16, Programming & reviewing – Heatcraft Refrigeration Products H-IM-79B User Manual

Page 15

Advertising
background image

1 5

PROGRAMMING AND REVIEWING SETTINGS/CHANGES (cont’d.)

Use this button to

“CLEAR/TEST”

Pressing this button ONCE

will return the LED display to the default

display. With the system in the

OFF

mode, pressing and holding

this button will start the

“TEST”

mode. In the “

TEST”

mode it will

cycle through each output for 10 seconds. The display will only
show “tst” during “

TEST

” mode. Test mode will automatically

terminate after 3 sequences.

STATUS INDICATOR LED

A RED, three-digit , alphanumeric LED on the Beacon II board indicates status, alarms and
error codes.

LED Display

• OFF

Box Temp

/

oFF

Box Temperature/ Mode is displayed

All Evaporators

• COOLING

Single Evaporator

-

Box Temp

/

Coo

Box Temperature/ Mode is displayed

Multiple Evaporators

Master Evap

-

Box Temp

/

Coo

Box Temperature/ Mode is displayed

Slave Evaps -

Coo

Operating Mode is displayed

• Pumpdown

All Evaporators

Pdn

• DEFROST

All Evaporators

dEF

• TEST

All Evaporators

tSt

• SERVICE

All Evaporators

SEr

• ALARMS

A 1

High Box Temp

A 2

Low Box temp

A 3

System Start-up

failure

Compressor does not start after three tries.
(Four minutes between each try)

A 4

Input Fault

Box Temp., Suction Temp., Pressure
Transducer open or not installed

Programming & Reviewing

LOCKING THE BEACON II BOARD

The Beacon II board is lockable to prevent programmed setting changes by unauthorized
personnel. When locked, the program setpoints cannot be changed.
To

lock

the setting:

Press “PROGRAM REVIEW” button.

Press and

hold

“MONITOR” button.

While holding

“MONITOR” button, press “ENTER” button.

The LCD will display

Loc

.

This will prevent unauthorized personnel program changes. To

unlock

, repeat steps above.

LCD will display “

UnL

”.

Advertising